Manual 37137B
ESDR 4 - Current Differential Protection Relay
Appendix C.
List of Parameters
Unit number
P/N _____________________________ Rev _______________________________
Version ESDR4 _______________________________________________________________
Project _____________________________________________________________________
Serial number
S/N _______________
Date
______________________________
Parameter Setting
Range
Default Customer
Settings
BASIC DATA
SPRACHE/LANGUAGE
english/german english
curr. transform.
ratio
10 to 6,000/x A
500/x A
generator nomin.
current
5 to 6,000 A
400 A
automatic reset
relay
ON/OFF OFF
ON
OFF
ON
OFF
CONFIGURATION OF PROTECTION
monitoring
ON/ OFF
ON
ON
OFF
ON
FF
release limit
IS/IN X=
50 to 300 %
100 %
release limit
Id/IN Y=
5.0 to 40.0 %
40.0 %
pick-up t. Id>IN
release
0.04 to 3.00 s
0.10 s
pick-up t. Id<IN
release
0.04 to 3.00 s
0.10 s
release time
release
0.1 to 3.00 s
0.10 s
automatic reset error text
ON/OFF OFF
ON
OFF
ON
OFF
automatic reset error text
1 to 60 s
10 s
warning
ON/OFF ON
ON
OFF
ON
OFF
warning limit
Id/IN Y=
3.0 to 40.0 %
30.0 %
pick-up time
warning
0.04 to 3.00 s
0.10 s
release time
warning
0.10 to 3.00 s
0.10 s
display value
Id in
[%] / [A]
[%]
%
A
%
A
display value
Is in
[%] / [A]
[%]
%
A
%
A
© Woodward