Items
Parameters
Defaults
Description
IDMT (Inverse
definite minimum
time)
If Type is »Define Time«:
Delay
0 to 3600 s
30 s
The alarm status change must be valid for this period of
time before it is released.
Note:
If delay time is set to Zero, alarm will be only a warning
alarm instead of a shutdown alarm.
If Type is »IDMT ...«:
Multiply
1 to 36
36
»Multiply« defines the grade of reaction on the ratio of
generator current to overcurrent setting. A low value means
fast reaction (short delay time); the greater the value the
slower reaction because longer delay time.
Monitoring Power
[PARAMETER / Configure monitoring / Generator / Power]
Items
Parameters
Defaults
Description
Overload
enabled/disabled
disabled
Notes
»enabled«: The following related settings will be taken into
account
Action
Not used
Warn
Shutdown
Not used
Alarm type to be released if wire break is detected.
There is no wire breaker for this protection.
Limit
0 to 6000 kW
304 kW
Release the alarm when sensor value is same or higher
than this value and Delay time is over
Return
0 to 6000 kW
290 kW
Reset the alarm when the active power os lower than this
value
Delay
0 to 3600 s
5 s
The alarm status change must be valid for this period of
time before it is released
4.2.5.2
Monitoring Breakers
Monitoring Breakers
[PARAMETER / Configure monitoring / Breakers]
Items
Parameters
Defaults
Description
Enable breaker feedback
monitoring
Enabled/disabled
Disabled
When breaker feedback monitoring is enabled, the device
uses the configured discrete inputs for the breaker status.
Check fail warn(ing)
Enabled/disabled
Disabled
Enable the breaker feedback monitoring. This requires the
"Enable breaker feedback monitoring".
Check time
0.0 to 20.0 s
5.0 s
Breaker monitoring delay time. After the configured check
time, a breaker failure alarm is activated.
53
easYgen-400
B37884A
4 Configuration
4.2.5.2 Monitoring Breakers
Released