7.5.2
Supported J1939 ECUs & Remote Control Messages
The following table lists all ECUs, which are supported by the easYgen beyond the J1939
standard with the appropriate settings. We recommend "Device type" (parameter
) "Standard" or "Standard C" for all ECUs, which are not listed here. All other
parameters shall be clarified with the ECU manufacturer.
ECU
Device type
(15102)
J1939
own
address
(15106)
Engine
control
address
(15107)
SPN
version
(15103)
Comment
Standard ECUs
Standard
Refer to
ECU
manual.
Refer to
ECU
manual.
Refer to
ECU
manual.
Please refer to
Types "Standard" and "Standard C"”
for more details.
Standard ECUs
(with message
counter and
checksum)
Standard C
Refer to
ECU
manual.
Refer to
ECU
manual.
Refer to
ECU
manual.
Please refer to
Types "Standard" and "Standard C"”
for more details.
Woodward EGS,
E3, E6, PG+
EGS Woodward
234
0
N/A
MTU ADEC ECU7
ADEC ECU7 MTU
1
128
N/A
The easYgen is connected with the
SAM via CAN. The SAM communicates
with the ADEC using an own bus.
Deutz EMR2
Volvo EDC4
EMR2 Deutz
3
0
Version 1
Deutz EMR3
Deutz EMR4
(EDC 17)
Standard
3
0
N/A
Volvo EMS2
Volvo EMS1
Volvo EDC3
EMS2 Volvo
17
0
N/A
The rated speed of the EMS1 and
EDC3 cannot be switched via the
easYgen.
Scania S6
S6 Scania
39
0
N/A
Scania S8
S8 Scania
39
0
N/A
MAN MFR/EDC7
MFR/EDC7 MAN
253
39
N/A
The easYgen is connected with the
MFR via CAN. The MFR communicates
with the EDC7 using an own bus.
SISU EEM2/3
EEM SISU
N/A
0 / (1)
N/A
Cummins
Cummins
220
0
N/A
Notes
Some Cummins setups need a special
value for “Governor Gain” otherwise
they will shut down. In this cases
please set the “Governor Gain” of the
ECU to »Internal« instead of »J1939«.
MTU ADEC ECU8/
ECU9
ADEC ECU8/9
MTU
234
0
N/A
The easYgen is connected with the
MTU system: ADEC ECU8 &
SmartConnect or ADEC ECU9.
Hatz EDC 17
Hatz EDC 17
3
0
N/A
ECU file
ECU file
N/A
This is to support ECUs which are not
represented by the selection. Enter file
837
easYgen-3000XT Series
B37574
7 Interfaces And Protocols
7.5.2 Supported J1939 ECUs & Remote Control Messages
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...