ID
Parameter
CL
Setting range
[Default]
Description
15154
Operation hours
source
2
This parameter configures the
source for the operation hours.
[Internal]
The operation hours are counted
internal from the easYgen
ECU/J1939
The operation hours are assumed
from the connected ECU (via
J1939 CAN protocol).
2509
Operation hours
preset
0
0.00 to 999,999.99
[0.00]
When setting the operating hours
counter (refer to parameter
), the counter always will be
set up to the value configured
here.
2574
Operation hours set
0
1
Yes
The current value of this counter
is overwritten with the value
configured in "Operation hours
preset" (parameter
After the counter has been (re)set,
this parameter changes back to
"No" automatically.
[No]
The value of this counter is not
changed.
Notes
1
The code level can be configured
with "Codelevel set operation
hours" (parameter
your current code level does not
match, this parameter is not
visible.
2573
Code level set
operation hours
5
0 to 5
[2]
This parameter defines which
codelevel is necessary to set the
operation hours (parameter
).
2515
Period of use preset
2
0.00 to 999,999.99
[0.00]
When setting the period of use
hours counter (refer to parameter
be set up to the value configured
here.
2579
Period of use set
0
1
Yes
The current value of this counter
is overwritten with the value
configured in "Period of use
preset" (parameter
After the counter has been (re)set,
this parameter changes back to
"No" automatically.
[No]
The value of this counter is not
changed.
Notes
1
The code level can be configured
with "Code level f. set period of
use" (parameter
). If
your current code level does not
match, this parameter is not
visible.
2581
Code level f.set
period of use
5
0 to 5
This parameter defines which
codelevel is necessary to set the
669
easYgen-3000XT Series
B37574
4 Configuration
4.10.2 Service Reset Values
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...