ID
Parameter
CL
Setting range
[Default]
Description
[1]
4.10
Configure Counters
General notes
The following chapters describe all available and configurable counters of the device.
The standard/basic counters - available in all devices of this product family - are
described in the chapter
╚═▷ “4.10.1 Generator Preset Values”
. For special counters
please see the chapters following.
4.10.1
Generator Preset Values
General notes
Maintenance call
A maintenance call will be issued if the configured number of maintenance hours has
expired or the configured number of days has expired since the last maintenance.
In case of a maintenance call, the display indicates "Mainten. days exceeded" or
"Mainten. hours exceeded".
ID
Parameter
CL
Setting range
[Default]
Description
2521
Gen.pos.active
energy preset
2
000000.00 to 999999.00 MWh
[0 MWh]
This parameter defines the
number of MWh of the counter.
The number entered here will
overwrite the current displayed
value after confirming with
parameter
2510
Gen.pos.active
energy set
2
Yes
The current value of this counter
is overwritten with the value
configured in "Gen.pos.active
energy preset" (parameter
). After the counter has been
(re)set, this parameter changes
back to "No" automatically.
[No]
The value of this counter is not
changed.
2523
Gen.pos.react.energy
preset
2
000000.00 to 999999.00 Mvarh
[0 Mvarh]
This parameter defines the
number of positive Mvarh of the
counter. The number entered here
will overwrite the current
displayed value after confirming
with parameter
.
2511
Gen.pos.react.energy
set
2
Yes
The current value of this counter
is overwritten with the value
configured in
"Gen.pos.react.energy preset"
665
easYgen-3000XT Series
B37574
4 Configuration
4.10 Configure Counters
Released