• Configure and check parameters at the easYgen (Select external terminals, Node-ID,
•
DI/DOs, AI/AOs)
Reboot the device that the setting (15320 ) becomes effective
• If WAGO terminals are connected and the configuration of the external AIs and/or
•
AOs is done, the easYgen must send a configuration string to the WAGO coupler one
time. This can be done by setting parameter »Configure external devices«
to "YES". This must be repeated if there is any change in number or kind of
WAGO modules.
• If you have changed parameter »Select external terminals «
: reboot the
•
device
• Set parameter »Configure external devices«
to "Yes"
•
• Verify the successful configuration of the external device(s)
•
Update WAGO After Any Change!
The update procedure described above must be repeated if there is any change in
number or kind of Wago modules.
ID
Parameter
CL
Setting range
[Default]
Description
9940
This device
2
Node-ID 1-126
[Node-ID 7]
The Node-ID for the control unit
(this device) is configured here.
9930
1st Node-ID
2
Node-ID 1-126
[Node-ID 1]
This Node-ID's are used for the
communication with CANopen
devices.
Parameter
external terminals" offers often
used pre-settings and the
possibility to point to a file
containing customer specific
settings.
9931
2nd Node-ID
2
Node-ID 1-126
[Node-ID 2]
9932
3rd Node-ID
2
Node-ID 1-126
[Node-ID 3]
9933
4th Node-ID
2
Node-ID 1-126
[Node-ID 4]
9934
5th Node-ID
2
Node-ID 1-126
[Node-ID 5]
9935
6th Node-ID
2
Node-ID 1-126
[Node-ID 6]
15320
Select external
terminals
2
Notes
A change of this parameter
becomes only effective if the
device is rebooted! and:
the external devices itself must be
configured with the correct node
ID.
624
easYgen-3000XT Series
B37574
4 Configuration
4.7.4.2.1 Expansion Modules at CANopen Interface
Released