ID
Parameter
CL
Setting range
[Default]
Description
) is configured to "3pos
controller".
5653
Expand deadband
factor
1
1.0 to 9.9
[1.0]
If the measured generator voltage
is within the deadband range
(parameter
configured delay expand
deadband time (parameter
) expires, the deadband will
be multiplied with the factor
configured here.
Notes
This parameter is only visible if
voltage control (parameter
) is configured to "3pos
controller".
5654
Delay expand
deadband
1
1.0 to 9.9 s
[2.0 s]
The measured generator voltage
must be within the deadband
range for the time configured here
in order to multiply the deadband
with the factor configured in
parameter
Notes
This parameter is only visible if
voltage control (parameter
) is configured to "3pos
controller".
5618
AM Voltage SP1 [V]
2
Determined by AnalogManager
81.09
[A1 = 05.57 Internal v setp1
[V]]
The voltage setpoint 1 source may
be selected from the available
data sources.
The internal voltage setpoint
05.57 can be changed manually at
the setpoint screen of the display.
Notes
The voltage setpoint may be
adjusted within the configured
operating limits (
Generator Operating Ranges:
Voltage / Frequency / Busbar”
5600
Int.voltage control
setpoint 1
2
50 to 650,000 V
[400 V]
The internal generator voltage
setpoint 1 is defined in this
screen. This value is the reference
for the voltage controller when
performing islanded and/or no-
load operations.
5619
AM Voltage SP2 [V]
2
Determined by AnalogManager
81.10
[A1 = 05.58 Internal v setp2
[V]]
The voltage setpoint 2 source may
be selected from the available
data sources.
The internal voltage setpoint
05.58 can be changed manually at
the setpoint screen of the display.
Notes
The voltage setpoint may be
adjusted within the configured
operating limits (
300
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.1 Voltage Control
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...