CPC-II Unit Replacement Procedure
10
Woodward
System preparation prior to CPC-II unit replacement.
“Master/Slave” indication shows only which unit is
designated for primary operation from the control
system. Because it is possible for the slave to be in
control, it is necessary to confirm which unit is
controlling the skid output via the external gages and
the “In Control” discrete output status.
It is possible to verify which unit currently is In Control in several ways (see below
points A, B, C):
A.
The system control pressure will be indicated on the center gage
(marked on hydraulic manifold with “CONTROL”).
The CPC-II currently controlling process will have a matching pressure indicated
on its gage (markings on hydraulic manifold: CPC-II Unit #1 pressure gauge
marked with “CPC 1”, CPC-II Unit #2 pressure gauge marked with “CPC 2”) .The
unit Not In Control or Failed should indicate a lower or zero (0) pressure.
Figure 2-2. Unit In Control verification using CPC-DX pressure gauges.
As shown in figure 2-3 below, the unit on the right (CPC 2) is in control and the
unit on the left (CPC 1) is not in control. In figure 2-4, the unit on the left (CPC 1)
is in control and the unit on the right (CPC 2) is shut down.
Figure 2-3. Unit In Control verification using CPC-DX pressure gauges
(Case: CPC-II Unit #1 and Unit #2 operate).
UNIT IN CONTROL