17.2 LUBRICATION

IIn addition to routine maintenance, motor bearings will, in the longer term, require attention. If motor bearings are greased 
through extended  lubricators, then the required quantity of grease must periodically be applied in accordance with 
information stated on the fan or motor nameplate and/or as per any instructions provided. A fully compatible grease type must 
be used, and it is essential that all traces of water and dirt are removed from around the grease points and that a clean grease 
gun is used. It is only necessary to apply a small amount of pressure when injecting the specified quantity of grease  
into the re-gearing point. If grease injection requires the maintenance engineer to apply a high pressure, then the cause should 
be investigated. Grease points are generally located close to the fan housing-mounted terminal box. Where motors require  
re-lubrication, a separate instruction is normally issued with each fan/motor configuration. This gives details of lubrication 
intervals and well as the type and quantity of grease to be used. 

If further details are required, Please contact Woods Air Movement USA directly.

17.3 INFREQUENT USE

If the fan assembly is used less frequently than once a month, or is designed for emergency-use only, the following additional
maintenance procedures must be carried out, and a record kept:

  -  Resistance of motor windings to earth, must be measured (at 500V dc) each month. If these readings are less than 10 MΩ 

(Megaohm), the motor must be dried out in a warm airflow (typically at +104°F) and re-checked before running the motor.

  -  The fan should be operated  between 15 and 30 minutes each month ensure  that correct  lubricant conditions are 

maintained within the bearings (i.e. to prevent grease hardening).

  -   An ‘emergency-use’ system should be run continuously for a minimum of fifteen minutes each month. The test should 

not only confirm that the fan operates correctly but must also ensure that the emergency use control system overrides all 
other control devices (except where matched frequency converters are used) (see Paragraphs 1 to 11 and 16.4 for more 
information).

  -  If space heaters / anti-condensation heaters are fitted, check each month that they automatically switch on (i.e. they are 

drawing current) when the motor is switched off.

18. OVERHAUL / EXTENDED MAINTENANCE

Advice on motor overhaul procedures, bearing /seal replacement, motor replacement, motor rewinding, spare parts, condition 
monitoring, vibration analysis, refurbishment, etc. is available from Woods Air Movement USA.

For emergency use fans, we recommend that motor shaft seals and bearings must be replaced after 20,000 hours or 5 years of 
normal operation whichever occurs first.

After 40,000 hours of running, we strongly recommend that a qualified and competent electrician performs a motor “health 
check” (as described  within section 8, Fault finding) to determine  the motor insulation condition.

Where the fan is to be used for an emergency (smoke extraction) operation, if motor insulation readings are less than 10 MΩ 
(Megaohm), then to ensure that adequate insulation life is available should the fan be required for emergency operation, we 
therefore recommend that the motor must be replaced with a new motor, which has been manufactured in accordance with 
current requirements as stated within the EN12101-3 specification

  

NOTE!

   

 When dealing with High Temperature Smoke Extract fans, only an authorized company may undertake the 
maintenance.  Failure to do so may invalidate our warranty. The motor manufacturer’s specification sheets are 
available through Woods Air Movement USA. After overhaul/extended maintenance the fan assembly must be 
correctly installed back into its original position in accordance Paragraphs 12, 13, 14 and 15 of this document.

After conducting overhaul /extended maintenance the fan assembly must be correctly installed back into its original position 
in accordance Paragraphs 12, 13, 14 and 15 of this document. For advice on “switching on” after maintenance, please refer to 
paragraph 16.5.

 

14

Содержание 911025

Страница 1: ...AEROFOIL AXIAL FLOW FANS HT STANDARD Safety installation and maintenance instructions Part Number 911025...

Страница 2: ...NTROLS 8 11 LONG TERM RELIABILITY 8 STANDARD VENTILATION FANS 12 SAFETY 9 13 INTRODUCTION PURPOSE GENERAL 9 14 STORAGE HANDLING 9 15 MECHANICAL INSTALLATION 10 16 ELECTRICAL INSTALLATION OPERATION 11...

Страница 3: ...NG INSTALLATION 17 2 FIXING ARRANGEMENT OF TERMINAL BLOCK DRAWING NO D258302 F 17 3 WIRING DETAIL THREE PHASE FANS WITH FAN HOUSING MOUNTED TERMINAL BOX 460V 208V 18 4 NOTES PAGE 19 THIS LEAFLET MUST...

Страница 4: ...foot mounted motor fitted then the motor mounting feet must be positioned underneath the motor Foot mounted motors must never be suspended from their mounting feet If in doubt please refer to Woods A...

Страница 5: ...ntilation mode Use of non approved drives is permitted as long as the drive is by passed from the control circuit once the fan is running at full speed Frequency converters also known as Variable Freq...

Страница 6: ...ng for unusual bearing noise more sophisticated equipment should be used to obtain a quantified bearing condition analysis Bearings must be lubricated to avoid metallic and direct contact of the movin...

Страница 7: ...ever be mixed with sodium or calcium based grease ATTENTION To avoid any eventual grease incompatibility always re grease bearings with the grease type indicated on the motor nameplate As a general ru...

Страница 8: ...ans therefore do not have re lubrication facilities Any old grease must be washed out with a designated solvent The bearings must be refilled with grease leaving the housing empty If a bearing is remo...

Страница 9: ...full fan motor nameplate details Should a fan failure occur whilst the product is under warranty then please contact Woods Air Movement USA before any repair work is undertaken If speed control is to...

Страница 10: ...nameplate For two stage contra rotating fans see Figure 1 on page 17 Sharp bends in the ductwork close to the fan must be avoided Adequate room must be allowed round the fan for inspection and mainte...

Страница 11: ...e earth must also be connected Sufficient cable length must be provided to allow for movement of the fan on its mountings A connection diagram providing wiring details is supplied with all fan assembl...

Страница 12: ...he electrical supply so that it will not automatically reset and re start If the fan is designed for emergency use then the control system must ensure that all monitoring devices are overridden so tha...

Страница 13: ...hen working in the vicinity of the fan assembly Fan assembly maintenance must be carried out by appropriately qualified and competent personnel using the correct tools and equipment A regular maintena...

Страница 14: ...correctly but must also ensure that the emergency use control system overrides all other control devices except where matched frequency converters are used see Paragraphs 1 to 11 and 16 4 for more inf...

Страница 15: ...has occurred which may require the motor to be either rewound overhauled standard temperature machines or replaced with a new motor which been manufactured in accordance with current requirements as...

Страница 16: ...fan housing is even and adequate If in doubt please contact Woods Air Movement USA for advice related blade tip gap Ensure that the impeller blades are secure Blade angle must not be changed before c...

Страница 17: ...Screw Locknut Terminal Screw Washer Customers supply Lead Eyelet when fitted Connecting Links when fitted Do not use Copper wire links Motor Lead Eyelet Terminal Screw Terminal Block Identification Ta...

Страница 18: ...TH TO S S S EARTH TO MOTOR T9 T1 L1 L2 T2 L3 T3 S L1 L2 L3 PE1 T1 T9 EARTH TO MOTOR MOD 18 T7 T6 T8 T4 T5 PE1 EARTH TO S S S S EARTH TO MOTOR T9 T1 L1 L2 T2 L3 T3 L1 L2 L3 PE1 T1 T9 EARTH TO MOTOR MOD...

Страница 19: ...19 NOTES...

Страница 20: ...ndustry application experience The widest range of Air Movement and Ventilation products in the market and strong market presence with over 100 years of experience and manufacturing of products guaran...

Отзывы: