FIREPLACE FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following
Figure 2
and the
chart below for your specific installation requirements.
See Figure 3 on Page 8
for firebox dimensions. The framing headers may
rest on the top of the firebox standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox
is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be installed on a
metal or wood panel extending the full width and depth of the enclosure.
Stud Location
Inside Chase Installation
Recessed Installation
Figure 2 - Framing Dimensions
Do not fill spaces around firebox with insulation
or other materials. This could cause a fire.
WARNING
Corner Location
6
7
BDV/HDV2000
BDV/HDV3000
A
33-
1/2"
37-
1/2"
B
32-1/2"
36-1/2"
C
20-
1/2"
22"
D
10-
1/4"
11"
E
50"
58"
F
25-1/4"
29"
G
B
D
H
15"
18"
36"
41"