WOODMASTER OUTDOOR FURNACES • OWNER'S MANUAL
6.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point
value.
2. The value of the set point will be displayed and the ˚F starts blinking.
3. To change the Set value push the UP or DOWN arrows within 10s.
4. To memorize the new set point value push the SET key again or wait
10s.
6.3 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing SET and DOWN keys for
three seconds (the ˚F LED starts blinking).
2. Select the required parameter. Press the SET key to display its value.
3. Use UP or DOWN to change its value.
4. Press SET to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting
for the time-out to expire.
6.4 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3s the UP and DOWN keys.
2. The "POF" message will be displayed and the keyboard will be locked.
At this point it will be possible only to see the set point or the MAX
(and) MIN temperature stored.
3. If a key is pressed more than 3s the "POF" message will be displayed.
6.5 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the UP and DOWN keys, until the
"Pon" message will be displayed.
7. PARAMETERS
REGULATION
Hy Differential: (1 ÷ 255 °F) Intervention differential for set point. Fan Cut
IN is Set Point Minus Differential (Hy). Fan Cut OUT is when the temperature
reaches the set point.