CLEARANCE TEST

Note : this test is to be conducted with the
firefront in position. Warm up the appliance
on MAX for ten minutes. Insert a smoke
match tube as shown in figure 11, 30mm from
either side of the fireplace opening, Smoke
should be drawn positively into the appliance.
If not repeat the test after a further fifteen
minutes. If smoke is still not positively drawn
into the appliance, isolate the gas supply to
the appliance and seek expert advice.

SERVICING AND MAINTENANCE

See convector instructions if your Airflame Excel mk.3 burner is installed within a
Wonderfire convector box.

Annual maintenance
The

The coals should be removed and any sooting carefully brushed from the surface
with a soft brush.

The coal matrix should be removed and any debris shaken off.  The burner should be
removed from the fireplace and any debris carefully removed using a soft brush.
Inspect the burner for any damage and repair or replace if necessary.  Please note
surface cracking of the burner is quite normal.

Check the venturi and injector for linting and clean if necessary.  Clean any debris or
carbon from around the pilot unit and check the correct operation of the gas control.
Reinstate the burner into the fireplace, reconnect the gas supply and check the
soundness of all gas connections. Refit the coals in accordance with the section of
this manual entitled, “Commissioning the burner”.

Follow the lighting procedure and check for spillage. If spillage is found the cause
should be identified and remedied.

Check any purpose made room ventilation is free from obstruction.

NEVER ATTEMPT TO INSPECT OR REMOVE THE FIRE UNLESS IT HAS BEEN
ALLOWED TO COOL FOR AT LEAST 15 MINUTES

The following procedures should be carried out with these tools at hand.

Slot head screwdriver

14mm spanner

7mm spanner

15mm spanner

10mm spanner

16mm spanner

11mm spanner

3/4 AF spanner

12mm spanner

Phillips No.2 type screwdriver

External circlip pliers

Figure 11

Содержание AF 18XL

Страница 1: ...18XL 9500360 AC 18XL 9500361 INSTALLATION SERVICING MANUAL Patent applied for 600B683 01 Please leave these Instructions with the user This Appliance is for use in the United Kingdom GB and the Repub...

Страница 2: ...pward draught is required for fires operating within standard fireplace openings Larger fireplace openings may require a correspondingly larger chimney diameter a faulty flue or chimney may result in...

Страница 3: ...xing screw and 1 x fibre rawlplug 9 1 x Smoke match tube TECHNICAL DATA Heat inputs gross AF18XL AF18XLP Minimum 5 8kW 7 6kW Maximum 10 5kW 9 0kW Setting pressures AF18XL AF18XLP Maximum cold 13 75mba...

Страница 4: ...appliance must not stand on combustible materials or carpets The minimum height from the top surface of the hearth to the underside of any shelf made from wood or other combustible materials is as fo...

Страница 5: ...ng procedure to establish the pilot and then turn to maximum setting Check the gas pressure against the setting pressures see gas data Turn off the fire and allow to cool COMMISIONING THE BURNER Placi...

Страница 6: ...t coal and the coal matrix In order to get the best flame effect it is important that the coals are evenly spaced and sit 10 15mm from each other Next take five random shaped coals and position as sho...

Страница 7: ...o ignition Two clicks will be observed and the pilot should ignite Hold the knob in this position keeping it depressed for ten seconds to allow the flame supervision device to establish Observe if it...

Страница 8: ...ol knob and turn clockwise until pilot setting is reached To Turn the Fire OFF Ensure control knob is in pilot position depress control knob and turn clockwise to the OFF position For fires fitted wit...

Страница 9: ...ush Inspect the burner for any damage and repair or replace if necessary Please note surface cracking of the burner is quite normal Check the venturi and injector for linting and clean if necessary Cl...

Страница 10: ...external circlip that retains the piezo unit Remove the piezo unit from the tap Replace in reverse order To remove the thermocouple pilot unit The thermocouple is an integral part of the pilot unit a...

Страница 11: ...PG 1 Excessive sooting can be caused by incorrect arrangement of the coals Ensure that the coal arrangement instructions given in this manual have been followed precisely 2 The position of the injecto...

Страница 12: ...se only the correct number of fibre bed components and install them as described in the procedures Description Wonderfire Part number Gas tap 9730084 Main injector AF18XL 9730091 Main injector AF18XLP...

Отзывы: