WOLSELEY Beermaster Plus BMIE-448-69 Скачать руководство пользователя страница 30

Cooling

30

BMIEP-133

Suction Line

Liquid Line

437

,2

389,2

1587,9

784,0

Access Panels Both Ends

400,0

450,5

Содержание Beermaster Plus BMIE-448-69

Страница 1: ...wolseley co uk climate Beermaster Plus Cooling Range Installationand maintenanceinstructions...

Страница 2: ...emperature 10 C Cellar Temperature 12 C 5 Pipework Installation Supports And Routing Page 10 6 Brazing Page 11 7 Expansion Valve Phial Location Page 11 8 Drainage Page 11 9 Electrical Supply Function...

Страница 3: ...e finished surfaces being damaged Units are not portable and are only for permanent installation CAUTION All work on the unit must be carried out by qualified personnel only The installation and maint...

Страница 4: ...d mitigation measures in place to prevent harm Refrigerant The system has been designed and certified when charged with R448a Charging with R449a is also acceptable Do not mix these refrigerants in th...

Страница 5: ...front two access panels Remove the front panel Rotate and slide the two side covers off the unit The covers will slide out of the from latches on the side of the unit and can then be set to one side C...

Страница 6: ...iling mounting or wall mounting For wall mounting the wall mounting kit optional must be used and is supplied as a separate order Locate the evaporator in accordance with the minimum clearances as det...

Страница 7: ...stallation of the mains cable The front controls facia will need to be removed CAUTION The plastic drain tray will need to be removed before any brazing is carried out the pipework This can be done by...

Страница 8: ...fixings provided Fix at all 4 positions tighten securely b Screw in the M8 fittings into the rails leaving a gap between the bolt and the bracket so that the keyhole fastenings can be positioned befor...

Страница 9: ...s to achieve the total equivalent run lengths When using the tables to determine pipe length round up the equivalent length and do not interpolate between values For example if the pipe run is between...

Страница 10: ...phere for any longer than necessary This causes moisture to be absorbed by the drier and reduces its normal system drying capacity The pipework bungs should only be removed just before brazing of the...

Страница 11: ...ions below 3 or 9 o clock position for 1 2 5 8 pipe 4 or 8 o clock position for 3 4 size pipe and above Do not mount the phial on the top or bottom of the pipe and ensure the full length of the phial...

Страница 12: ...rminated at a wall mounted junction box or isolator close to the unit and a reduced size cable is used to connect the junction box isolator to the unit Cable connection termination There is no interco...

Страница 13: ...ud provided The supply L N cable cores should be routed into the control box via the conical grommet as shown circled below Power entry points Conical grommet For access to the control box the 6 fasci...

Страница 14: ...d and ensure all paths are open Evacuate the system to below 225 microns 0 3 mbar The pump should be isolated and the system pressure monitored A rapid continuous rise in pressure would indicate a lea...

Страница 15: ...of turns with the system being allowed to settle for at least 10 minutes after each adjustment has been made Once charged if the unit is left with the power supply turned off the crankcase heater shou...

Страница 16: ...ompressor is running If the compressor rotation is incorrect the compressor will be very noisy and current draw substantially reduced Correct the rotation by swapping over any two of the supply phases...

Страница 17: ...differential setting as below Lower set point cut out pressure Upper set point cut in pressure differential The default settings are as below Upper set point 5 barg Differential 3 barg This gives a de...

Страница 18: ...the installer s responsibility to decide to fit the cover or leave uncovered If the isolation cover is used then potentially an auxiliary emergency stop may need to be incorporated as part of the ins...

Страница 19: ...rder to use defrost As per below on evaporator energy saving this means that the relevant jumper must be in the C position Please see on evaporator energy saving for instructions on how to change this...

Страница 20: ...ans that the controller is set to run only the first fan when off cycle or in heating mode As a result this significantly reduces energy consumption where there are multiple fans In order for the cont...

Страница 21: ...below Turn off and isolate the power to the BMIEP unit Remove the front cover from the control s facia Find the small jumper labelled 1400 1000 and 1600 1200 This is located to the left of the energy...

Страница 22: ...rator must be selected to be the master unit and the other BMIEP the slave unit 2 Isolate the electrical supply to all units 3 Open the slave BMIEP controller front fascia and remove the display lead...

Страница 23: ...ns Every 12 months Check security of fixings especially the fan and motor mountings Check refrigerant pipeline for damage and leaks Check evaporator and condenser motors fans should rotate freely Chec...

Страница 24: ...tibility Regulations 2016 EN 61000 6 1 2007 Electromagnetic compatibility EMC Generic standards Immunity for residential commercial and light industrial environments EN61000 6 3 2007 A1 2011 Electroma...

Страница 25: ...rpm ON CYCLE 1400rpm OFF CYCLE 1000rpm BMIEP 448 37 52 45 50 44 52 45 50 44 BMIEP 448 48 BMIEP 448 69 55 45 54 44 55 49 54 47 BMIEP 448 89 BMIEP 448 133 57 45 55 44 57 51 55 49 SOUND PRESSURE db A 3m...

Страница 26: ...Cooling 26 23 Sales outlines BMOP130 BMOP250...

Страница 27: ...27 Cooling BMOP 320 350 360...

Страница 28: ...Cooling 28 BMIEP 37 48 Suction Line Liquid Line 437 0 389 2 470 0 370 0 Access Panels Both Ends 400 0 449 5...

Страница 29: ...29 Cooling BMIEP 69 89 Suction Line Liquid Line 437 0 389 2 1162 9 582 5 Access Panels Both Ends 400 0 450 5...

Страница 30: ...Cooling 30 BMIEP 133 Suction Line Liquid Line 437 2 389 2 1587 9 784 0 Access Panels Both Ends 400 0 450 5...

Страница 31: ...7 83 32 32 2 5mm 4 0mm BMOP320 3 11 6 30 16 16 1 5mm 1 5mm BMOP350 3 11 5 30 16 16 1 5mm 1 5mm BMOP360 3 15 9 43 20 20 2 5mm 2 5mm BMIEP running amps EVAPORATOR UNIT MODEL FAN MOTOR HEATER MOTOR RATE...

Страница 32: ...Cooling 32 BMOP 1PH BMO PLUS 1PH Schem Rev1...

Страница 33: ...33 Cooling BMOP 3PH BMO PLUS 3PH Schem Rev1...

Страница 34: ...Cooling 34 BMIEP All Units...

Страница 35: ...invalidate the warranty The item may be replaced or rectified if the guarantee claim is valid For items that have been installed Wolseley have the right to decide if rectification on site is suitable...

Страница 36: ...wolseley co uk climate Kelvion BMI BMO Installation and maintenance Issue 1 0 2021...

Отзывы: