1. Switch the cascade controller N1 to emissions test, then press and hold
down the rotary selector (see RK-2 / RK-4 installation and operating
instructions, page 112).
2. Switch ON the ON/OFF switch
!
.
Remove the rotary selector
"
from the boiler thermostat.
Push down the high limit safety cut-out test button using a suitable
instrument, for example a phase tester, and hold it down until the limiter
responds.
Replace the rotary selector on the boiler thermostat.
Repeat the test for N2 and the boiler control unit of boiler no. 2.
Reset the high limit safety cut-out after the boiler has cooled down.
End of function check.