4. Specification
Max. spread
A cast section protection function is integrated in the MGK-2. This prevents stresses in
the material by limiting the maximum temperature differential between the flow and
return. As of 28 K, the output is reduced. If 40 K is nevertheless reached, the burner
shuts down briefly without a fault message. This characteristic must be taken into account
when selecting the components (e.g. pumps, heat exchanger and cylinder).
Flow rate
Excessive flow velocities may lead to erosion.
Maximum flow rate (volume flow) at Q
max
:
MGK-2-390: 28.5 m³/h
MGK-2-470: 34.4 m³/h
MGK-2-550: 39.8 m³/h
MGK-2-630: 45.5 m³/h
MGK-2 heating water pressure drop:
Heating water pressure drop [mbar]
Throughput [m³/h]
MGK-2-550
MGK-2-630
MGK-2-470
MGK-2-390