Installation
38 | WOLF GmbH 3066501_201910
5.9
Connecting the balanced flue
► Comply with the planning guidance
250
50
50
DN60/100: 235
DN80/125: 200
90
Fig. 5.14
Example: balanced flue [mm]
q
Heat generator
w
Appliance connection with flue gas test port
e
Inspection piece
r
Balanced pipe flue
t
Disconnect device
y
Spacer clip
5.9.1
Installing the balanced flue
Installation information for balanced flue system
NOTE
Inadequate incline for balanced flue!
Corrosion of components or faults.
► Install the balanced flue with an angle of at least 3° (6 cm/m) relative to the heat generator.
► Follow the installation instructions for the balanced flue system.
► Never install damaged parts.
► Create flue connections using sockets and gaskets.
► Ensure that gaskets are fitted correctly.
► Always arrange sockets against the direction of the condensate flow.
► Always trim the flue on the smooth side,
never
on the coupling side.
► Bevel or deburr trimmed flues to ensure gas-tight installation of pipe joints.
► Remove contamination before installation.
► Wet or lubricate all air/flue gas joints prior to installation, e.g. using soap suds or a suitable grease
without silicone.
► Lines must be secured with brackets.
Connecting the appliance connection with flue gas test port
► Install appliance connection with flue gas test port
(2)
Fig. 5.14 Example: balanced flue [mm]
) at the
connection point of the heat generator
(1)
.
Fit inspection piece
If an inspection aperture is required for the balanced flue,
► insert a balanced flue pipe with inspection aperture.