42
No.
Faults
Effect
Cause / Remedy
15
Outside temp
sensor
(value is no longer
shown on display)
Control functions depending on
outdoor sensor are no longer
supported (night ventilation,
natural cooling, etc.).
Sensor or lead faulty.
Carry out sensor detection.
111
112
E112 EEPROM-Sys
Syspar - Chksum
(Fault message on
starting)
System fails to start
Initialisation failed
Press key 3 x
200
Fire alarm
Depending on parameter
settings, the system stops or
only a fault message is issued.
Once the fault is remedied
and the fault message is
acknowledged, the system
starts again.
Fire alarm, fire damper has
responded.
204 Ice sensor
HR shuts down
and/or is no longer controlled.
Analogue output Y3 is set to
"0". Temperature control via
the heating valve continues as
normal.
Faulty sensor or sensor lead,
or temperature fallen below the
sensor's limit temperature
205
Condensate
The affected fan stops. All
outputs are set to "0".
Function
only available in active cooling
mode
.
Once the fault is remedied
and the fault message is
acknowledged, the system starts
again.
Condensate hoses contaminated
or kinked.
The condensate is no longer
being pumped away.
207
Motor protection
The affected fan stops. All
outputs are set to "0".
Once the fault is remedied
and the fault message is
acknowledged on the BML, the
system starts again.
Temperature in the fan motor
has exceeded the permissible
range.
With EC fans, the motor must be
switched off for about 1 min. in
order to reset the fault.
209 Supply air sensor The ventilation unit for the
affected zone stops. All outputs
are set to "0".
Sensor or lead faulty.
210
Room sensor
(extract air
sensor)
The ventilation unit for the
affected zone stops. All outputs
are set to "0".
Sensor or lead faulty.
Fault messages