English
Broome 10 Installation Manual
8
9. Technical data
All figures are typical values at 400 Vac, 50 Hz input voltage, 24 V, 10 A output load, 25°C ambient temperature and after
a 5 minutes run-in time unless otherwise noted.
Device supply
Input voltage
380 V – 480 V AC
- 10 % / +15 %
Mains frequency
50 – 60 Hz
± 6 %
Input current AC
0,77 / 0,62 A
At 400 / 480 Vac
Power factor
0,70 / 0,73
At 400 / 480 Vac
Output
Output voltage
24 V DC
0 % / + 6 % over entire load range
Adjustment range
-
Not adjustable
Output current
10 A
5 A
Below + 50°C ambient
At + 70°C ambient
Derate linear b 50°C and + 70°C
General data
Size (W x H x D)
45 x 160 x 130 mm
Weight
550 g / 1.21 lb
Efficiency
94,9 / 94,8 %
At 400 / 480 Vac
Power losses
12,8 / 13,2 W
At 400 / 480 Vac
Temperature range
- 25°C to +70°C
Input inrush current
1,5 / 1,5 A pk
At 400 / 480 Vac
Hold-up time
20 / 20 ms
At 400 / 480 Vac
Connection data
Max. wire size
1)
2.5 mm
2
/ 2.5 mm
2
Output, DC-OK terminals
Max. wire size with ferrules
1.5 mm
2
Output, DC-OK terminals
Wire size range AWG
AWG 24-12
Output, DC-OK terminals
Max. wire diameter
2)
2.3 mm
Output, DC-OK terminals
Wire stripping length
10 mm / 0.4 inch
Output, DC-OK terminals
1) Solid / stranded wire