Wise P941 Скачать руководство пользователя страница 4

 1. Introduction

 P941, P942 is a pressure switch product with a built-in micro switch, and is so designed

that it can be used for corrosive fluid or high pressure process.  

The switch is divided into a sensor part under pressure, a control part that regulates 

the set value and inflow pressure, and a micro switch that gives contact output. 

Micro switch is a high-precision product designed so that it can be operated by 

minute pressure change, and has various rated current values. Please correctly use  

this product after having thorough knowledge of this instruction manual that states 
how to use it respectively in case of intending to use this product.  

 2. Features

 This product can be used for turning on an abnormality alarm or warning light, or 
process control according to ON-OFF signal in case of reaching the set pressure. 
And it cannot be used in explosion proof area. 

 3. Specification and standards

1) Nominal diameter

: PN941 - Single set point

              129.2(W) X 146(H) X 62.5(T)

: PN942 - Dual set point

              129.2(W) X 146(H) X 92(T)

2) Repeatability

: ±0.5% of Adjustable Range

3) Materials of wetted part

: Stainless Steel 316LSS

4) Working temperature

: -20 ~ 60℃

5) Number of contacts

: 1X SPDT or 2 X SPDT

6) Electrical properties

Resistance load

Inductive load

125V AC  15A

250V AC  15A

30V DC     1A

Insulation

resistance

100MΩ or more

on 500VDC

( Between each

terminal and case )

Withstand

voltage

1500V AC,

50/60Hz

one minute

( Between each

terminal and case )

Rated voltage

125V DC 0.05A

125V AC   15A

250V AC   15A

30V DC     2A

125V DC  0.5A

Содержание P941

Страница 1: ...INSTRUCTION MANUAL MODEL P941 P942 ITEM PRESSURE SWITCH ...

Страница 2: ...se a cable gland of the same class or upper class 8 Please construct wiring in accordance with consumers electrical installation guide and electrical facilities technical standards 9 Make sure to turn off the valve to prevent the measuring fluid leak when dismounting the gauge 10 Use a pressure gauge with no oil in an environment with hydrocarbon or oxygen Oil contained in the gauge may react with...

Страница 3: ...RES 3 SPECIFICATION AND STANDARDS 4 STRUCTURE AND FUNCTION 5 OPERATING PRINCIPLE 6 TRANSPORTATION STORAGE AND OPENING 7 CONTACT POINT WORKING TYPE AND CONNECTION 8 INSTALLATION 9 WIRING 10 MAINTENANCE AND OPERATION CONTENTS ...

Страница 4: ...oduct 2 Features This product can be used for turning on an abnormality alarm or warning light or process control according to ON OFF signal in case of reaching the set pressure And it cannot be used in explosion proof area 3 Specification and standards 1 Nominal diameter PN941 Single set point 129 2 W X 146 H X 62 5 T PN942 Dual set point 129 2 W X 146 H X 92 T 2 Repeatability 0 5 of Adjustable R...

Страница 5: ...ion P941 P942 Dead Band within of F S 0 1 0 0 1 0 1 0 0 1 15 0 1 0 2 0 0 2 10 0 1 0 3 0 0 3 0 1 0 4 0 0 4 8 0 1 0 6 0 0 6 0 1 1 0 1 6 0 1 1 5 0 1 5 0 1 2 0 2 0 2 5 0 3 5 0 5 0 7 0 35 0 10 0 15 Pressure Gauge Mpa Compound Gauge Mpa Vacuum Gauge Mpa 15 0 02 0 1 0 25 ...

Страница 6: ...tion in case of storage Please store it at the place with little humidity and the place where there is no vibration and dust In case of multi level stacking the weight should be to a degree where packing box isn t deformed And always store the product so that it cannot fall 3 Attention in case of opening a package Please carefully handle the object in case of opening a package Please take out the ...

Страница 7: ...ture than specified in this manual 3 Be prepared for lightning or vapor 4 Avoid direct sunlight 5 Use M5 bolts when fixing the product to the panel or wall through fixing holes When you use fittings fix them firmly 6 Use a flexible tube for the impulse line to prevent excessive force on the pressure gauge 7 For pipe connection do not grab and turn the product case rather use a designated spanner ...

Страница 8: ...dication instrument makes a big error remove it from the product for inspection It may have been caused by wear corrosion external shock vibration or shock of a part In this case you must remove adjust or exchange the part 8 Standard rated current is based on 3 6 However it may be different in case of having a MICRO S W built in Therefore please use it with a tolerance in consideration of inrush c...