 8. HOW TO SET

Set point can be altered by turing the screw inside the gauge. Setting method can be
differentiated by its contact type.
 -  HIGH

When rising pressure reaches at a set point, the switch status becomes "ON."
Adjust the setting pointer from High to Low pressure .

 -  LOW

When decreasing pressure reaches at a set point, the switch status becomes "ON."
Adjust the setting pointer from Low to High Pressure set point.

 9. Maintenance and Operation

1) The commercial pressure shall be below 75% of the max graduation.
2) Do not impose a pressure beyond the allowable limit.
3) Avoid sudden pressure surge or drop.
4) If there is a risk of pulsation or impact pressure, install overpressure protection device 

like dampener or gauge protector.

5) Do not grease the operation parts in the pressure gauge.
6) The regular inspection shall be made once or twice in 6 months to check contact operation.
7) If the indication instrument makes a big error, remove it from the product for inspection.

It may have been caused by wear, corrosion, external shock, vibration, or shock of a part.
In this case, you must remove, adjust, or exchange the part.

8) The standard rated current shall follow 4. 7) but it may be different when the product is 

equipped with a special micro software. Please, add some allowance to the rated current 
 written in this product, considering the inrush current.

9) Before you open or close the cover for pressure gauge repair or inspection, be sure to shut 

off the power. 
Malfunctioning of the switch may ignite the explosive gas in the gauge.

접단차

0

최고압력

(Differential Gap)

설정치

설정눈금

설정침

설정조정축

설정치

(MAX.PRESSURE)

(SET POINT)

감압(DECREASING PRESSURE)

승압(RISING PRESSURE)

(SET POINT)

(SETTING SCALE)

(SETTING POINTER)

(SETTING SCREW)

접단차

0

최고압력

(Differential Gap)

설정조정축

설정침

설정눈금

설정치

감압(DECREASING PRESSURE)

승압(RISING PRESSURE)

설정치

(SET POINT)

(MAX.PRESSURE)

(SET POINT)

(SETTING SCALE)

(SETTING POINTER)

(SETTING SCREW)

Содержание 531 Series

Страница 1: ...USER MANUAL MODEL P510 P520 531SERIES ITEM ELECTRIC CONTACTS TYPE PRESSURE GAUGE ...

Страница 2: ...ore removing This will prevent the fluid or other substances to release This release might cause the destruciton of surroundings 6 Use Use No Oil Pressure gauges for the environment where Hydrocarbon or Oxygen is present General Pressure gauges with the left over oil inside can lead to explosion when it gets mixed with oxygen or Hydrocarbon 7 When installing the product please follow the instrucit...

Страница 3: ...ICATIONS 3 FEATURES 4 SPECIFICATION AND STANDARDS 5 STRUCTURE AND FUNCTION 6 OPERATING PRINCIPLE 7 CONTACT POINT WORKING TYPE AND CONNECTION 8 HOW TO SET 9 MAINTENANCE AND OPERATION 10 USE 11 INSTALLATION 12 WIRING CONTENTS ...

Страница 4: ...the switch is mounted 3 A contact switch pressure indicating has separate indicator and setting scales for easier setting 4 Specification and Standards 1 Norminal diameter 100 and 160mm 2 Accuracy Indication range 1 0 of Full Scale Alarm setting 1 0 of Full Scale 3 Materials of wetted part Stainless Steel 4 Connection type 3 8 1 2 PT NPT PF 5 Number of contacts 1 X SPDT or 2 X SPDT 6 Working tempe...

Страница 5: ...es 5 Structure and Function Setpoint Adjustment Dial Cap Terminal Box Indicator Process Connection NO 2 Setting Pointer NO 2 Setpoint Indicator Scale Plate NO Description Remark NO 1 Setting Pointer NO 1 Setpoint Indicator ...

Страница 6: ...4mm and its principle is to point currently applied pressure by using a turn angle 270º Therefore Bourdon Tube and Movement are the most important and these parts must be well assembled in the pressure gauge because these parts leads to precise machining accurracy 7 Contact Point Working Type and Connection 1 HIGH ALARM As a Single Contact when the pressure reaches higher than its set point User c...

Страница 7: ...2 3 0 4 1 5 2 6 3 상한접점 검정색침 연결단자 1 2 하한접점 적색침 연결단자 6 5 설정치 최대압력 SET POINT MAX PRESSURE CONNECTION BOX 단자대 MICRO SWITCH 마이크로 스위치 HIGH CONTACT BLACK POINTER LOW CONTACT RED POINTER CONNECTION TERMINAL CONNECTION TERMINAL 0 4 1 5 2 6 3 상한접점 검정색침 연결단자 1 2 상한접점 적색침 연결단자 5 4 설정치 최대압력 SET POINT MAX PRESSURE CONNECTION BOX 단자대 MICRO SWITCH 마이크로 스위치 HIHIGH CONTACT BLACK POINTER HIGH CONTACT RED POINTER CON...

Страница 8: ...wice in 6 months to check contact operation 7 If the indication instrument makes a big error remove it from the product for inspection It may have been caused by wear corrosion external shock vibration or shock of a part In this case you must remove adjust or exchange the part 8 The standard rated current shall follow 4 7 but it may be different when the product is equipped with a special micro so...

Страница 9: ... 11 Installation 1 Install in a place devoid of moisture vibration dust or corrosive gas 2 Avoid areas that might exceed the temperature ranges specified in this manual 3 Make sure to protect from lightning or steam 4 Avoid areas with direct sun light 5 Use M5 nuts and bolts to mount on a panel or wall using the mounting holes If mounting brackets are used make sure it is installed securely 6 Inle...

Отзывы: