Shadow VI User Manual
page 58
Chapter 2
Installation and Checkout
MPCE Monitor Inputs
DANGER
!
MPCE INSTALLATION NOT SUITABLE FOR SAFETY USE
•
Install MPCE relays in pairs as instructed in this manual.
•
Use only relays with forced guided type contacts for MPCE monitoring.
•
Ensure that the response time of the MPCE circuitry is less than 25 ms.
•
Use only the safety outputs for personnel protection.
Failure to comply with these instructions will result in death or serious injury.
To monitor the performance of your relays with the Machine Primary Control Element
(MPCE) monitor inputs, connect the Shadow stop circuits to the interfacing relays, instead of
connecting them in series with the machine’s immediate stop circuit or with control reliable
safety relay modules.
See the figure below for an example of how to wire the MPCE inputs. Use normally closed
contacts only. To monitor external MPCEs, place jumpers J14 and J15 in the EXT (external)
position. See Figure 2-23. Call Wintriss Tech Support for further information.
Machine Primary
Control Element
(MPCE) Relays
2
3
11
5
4
6
3
8
1
7
2
K1
5
4
6
3
8
1
7
2
K2
FSD1
FSD2
Light Curtain
Control
6
5
US ER POWER
MPCE1
MPCE2
UPPER
TB4
UPPER
TB4
LOWER
TB4
12
13 14
Figure 2-21. Example of MPCE Usage
Содержание Shadow VI
Страница 142: ...1107200 Shadow VI User Manual page 130 Appendix C Installation of Shadow VI WPC Control Board ...
Страница 144: ...1107200 Shadow VI User Manual page 132 Appendix D Replacement Parts ...
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 157: ......
Страница 158: ......
Страница 159: ......