AutoSet User Manual
1137200
Operation
4-13
1.
On standard AutoSets, press the RESET button and hold for at least two seconds or until
the Setpoints LED displays flash once and change to 120% of full-scale tonnage
or
On AutoSet Plus units, turn the DISPLAY switch to the RESET position and hold for at
least two seconds or until the Setpoints LED displays flash once and change to 120% of
full-scale tonnage.
2.
Start the press. AutoSet will recalculate setpoints after the sample period is completed and
display them in the Setpoints LED displays.
On AutoSet Plus units, Setpoints displays show high tonnage setpoints if the DISPLAY
switch is turned to the HIGH position and repeatability setpoints if the DISPLAY switch is
turned to the REPEATABILITY position.
Displaying Reverse Load (AutoSet Plus Only)
AutoSet 1500 Plus and 1504 Plus load analyzers enable you to display reverse tonnage. To do
so, perform the following step:
1.
On the AutoSet front panel, press the REVERSE button. As shown in Figure 4-5, the
message “reV” appears in the Setpoints LED displays, and the reverse tonnage appears in
the Load displays.
Figure 4-5. AutoSet 1504 Plus Front Panel Showing Reverse Tonnage LED Displays
AutoSet 1504
®
WINTRISS LOAD ANALYZER
PLUS
REVERSE
button
SETPOINTS
RIGHT
LEFT
ZERO CAM
REAR LOAD
SETPOINTS
FRONT LOAD
TOTAL
DISPLAY
HIGH
RESET
REPEATABILITY
REVERSE