Instructions premix Air heaters type XR10.. 60
Page 3/15
!
!
!
!
" #$
" #$
" #$
" #$
The premix unit air heater is provided with sophisticated control sequence to maintain a
comfortable room temperature and even air distribution.
It is paramount that that the installation and maintenance of this appliance are carried out by
qualified gas engineers, and strictly according to our instructions.
Before unpacking and installation, please check (i.e. on the data badge) if the heater is in
accordance with the order and if it is suitable for the local present provisions (gas type, gas
pressure, electrical supply etc.)
The installation of this appliance must be in accordance with the relevant requirements of the
gas safety regulations building regulations (and the IEE regulations ) and any requirements of
the Local Authority , Fire Officer and Insurers.
The heater must also comply with all applicable local and national standards.
The heater has been tested in detail on safety and correct operating settings before leaving the
factory. It has been adjusted for the type of gas that is stated on the data badge. Should there
be any doubt , please contact the manufacturer.
%
%
%
%
&&$ #
'
'
&&$ #
'
'
&&$ #
'
'
&&$ #
'
'
The installation of the air heater must be in accordance with the relevant
requirements of the Gas Safety regulations (for example in GB; The Institute of Gas
Engineers IGE UP-1 and 2), building regulations and the IIE regulations also
incorporating the gas safety (installation and use) regulations. Other national and/or
local regulations may apply! The competent installer must make sure the heater operates
correctly and must instruct the user about the safe operation of the heater.
A ventilation gap of 30 cm is required from the top and bottom of the heater to any flammable
materials.
If this heater is drawing its combustion air from within the room in where it is located, the
necessary combustion ventilation requirements must be allowed for as per the gas safety
regulations. The heater should not be directly installed in areas containing any corrosive or
explosive vapours , in high moisture or dust concentrations, at negative pressures or
temperatures higher than 30°C ; please consult Winterwarm or your supplier. The guarantee is
then invalidated. The heater has a protection degree of IP20, this means for use in a dry and
not very dusty environment. This is also the case for the Open-therm room-thermostats.
Make sure that the warm air can be blown out freely. There should absolutely be (no possibility
of) materials within 5m from the front of the heater.