23
INSTRUCTION MANUAL
AIR HEATER TYPE XR+
CAUTION!
Always check for gas leaks after working on
the air heater.
CAUTION!
Do not use water when cleaning the air heater.
CAUTION!
The heater must be electrically isolated during
servicing.
10.2 Basic maintenance
To perform basic maintenance on the air heater, do the
following:
CAUTION!
When cleaning parts of the air heater, use
a dry cloth, brush, compressed air or a vacuum cleaner.
Never use a steel brush.
1. Inspect the outside of the heat exchanger.
2. Clean the fan guard on the outside of the heater.
Clean the fan blades if required.
3. Open the access panel.
4. Clean the inside of the air heater. Focus on the fol-
lowing parts:
–
Body
–
Fan blades and motor
–
Heat exchanger
–
Temperature sensor
–
Vane switch (if present)
5. Check if the wiring, nuts and bolts are properly
secured and tightened.
6. Grease any parts and bolts that are regularly loos-
ened for maintenance.
7. Open the manual gas valve in the supply line and
check if the supply lines are air tight, do not leak
and do not contain air.
Some checks can only be performed when the heater is
running. Do the following:
1. Reconnect the air heater to the power supply.
2. Switch on the air heater.
3. Check if the heater operates without problems. See
chapter if any errors occur.
4. Check the air heater’s combustion efficiency. If
necessary:
–
Adjust the burner settings (see §7.1).
10.3 Maintenance of the burner unit
The burner unit is an important part of the air heater and
requires special maintenance.
To perform maintenance on the burner unit, do the
following:
1. Remove the gas pipe between the gas valve and
the combustion fan.
2. Remove the ignition and fan wires.
3. Unscrew the socket screws (M6).
4. Remove the burner unit from the air heater, com-
plete with flange and pre-mix fan.
5. Disassemble the burner unit.
6. Adjust the ignition electrode:
a. The distance between the electrode and the
burner should be (±) mm (figure 21).
b. The distance between the two electrodes
should be (±) mm (figure 22).
c. Check the setting of the ignition electrode.
The spark should be formed between the two
electrodes, not between the electrode and the
burner.
Figure 21 - Distance between the electrode and the
burner
Figure 22 - Distance between the two electrodes
7. Reassemble the burner unit and install it back in
the air heater.
–
Use new gaskets.