Instructions condensing Air heaters type XR version XR-GB-4001-a
Page 19/27
L-20
Flame error
Flame failure during burning detected
5
L-25
Sensor
error
Sensor heat exchanger fault
4
L-26
Sensor
error
Flue sensor fault
4
L-27, 28,
29, 30,
31
Internal
error
Internal error
13
L-32
Sensor
error
Sensor heat exchanger fault
4
L-33, 34,
35, 36,
37, 38
Internal
error
Internal error
13
Temperately errors, the will disappear when the cause is taken away
Display
Explanation
Cause
E00, to
04
Internal
error
Internal error
13
E-05
Overheat
Overheat heat exchanger sensor
3
E-06 to
13
Internal
error
Internal error
13
E-14
Flame error
Flame detection when that should not be
16
E-15 to
22
Internal
error
Internal error
13
E-23, 24 Flue sensor Flue sensor not detected
E-30-31
Flue sensor Flue sensor shortened
E-34
Reset
button
Too many reset actions in a short time
9
E-36
Overheat
Overheat heat exchanger sensor
3
E-38, 39 Heat
exchanger
sensor
Sensor heat exchanger not detected
4
E-48, 48 Heat
exchanger
sensor
Heat exchanger sensor shortened
4
Case 1:
Within 5 sec flame, then flame failure.
•
The flame is not detected. Check the ignition cable and electrode. (cable resistance 1k
Ohm).
•
The electrical earth of the heater is poor,
•
The print board is defective.
Case 2:
•
There is not enough gas pressure.
•
The mixture of gas/air is poor, adjust the gas valve
•
The gas valve does not open, check during ignition for 230V on the valve.
•
Check whether the ignition electrode sparks, replace cable, electrode
Case 3:
Heat exchanger too hot
•
Check whether the system fan blows enough air.
•
Check the setting of the gas valve, the heater may me overloaded.
Case 4:
Temperature sensor on heat exchanger error.
•
The sensor has internally 2 sensors. These differ too much. Measure the resistance
from each sensor, the resistance should be 20K at 25° en 25K at 20°. If the measured
values differ too much, replace sensor.
•
L-25 is heat exchanger sensor, L-26 is flue sensor
Case 5
: Too many flame failures while burning
•
The setting of the gas valve is not ok, adjust the gas valve
•
The flue outlet is blocked