INSTALLATION MANUAL    AIR HEATER TYPE EH  8 

4.3 Electrical connection 
 

The electrical installation must comply with 
local and national requirements as well as IEE 
regulations. 

 

4.3.1 Power supply 
 

The air heater requires an earthed power 
supply of 230 V/AC. A supply of 400 V/AC + 
Neutral is optional. The control circuit is a two 
wire low voltage bus communication. 

 

4.3.2 

Fuse 

One fuse is present on the air heater’s control 

board (see the electrical wiring diagram in §9).  

• 

When replacing this fuse, always use a 

fuse of the same type (5AT). 

 

4.4 Room thermostat 

The heater can only be controlled with one of 
the following Winterwarm modulating room 
thermostats: 

-

 

The MTC

: a modulating digital clock 

thermostat with optimiser. 

-

 

The MTS

: a modulating digital 

thermostat. 

-

 

ON/OFF thermostat: 

a simple on/off 

thermostat. 

-

 

Interface module

; a specially designed 

interface module for BMS systems. 
Contact your supplier for more 
information. 

4.4.1 Installation requirements

 

 

Follow these requirements when placing the 
thermostat to ensure the heater functions 
correctly: 

• 

Make sure that air can circulate around the 

thermostat

  

• 

Make sure the sun does not shine directly 

upon the thermostat

• 

Do not place the thermostat on a cold wall.  

• 

Place the thermostat on an inner wall free 

from draught. 

• 

Never place the thermostat within the throw 

of the heater.  

• 

Never mount the thermostat near the 

aerials of internal communication 

networks. These emit radiation that can 

disturb the thermostat. Keep several 

meters distance. 

 

In all cases, the communication between the 

heater and the thermostat is based on a two 

wire, low-voltage connection. (see the 

electrical wiring diagram in §9). Follow these 

instructions to prevent malfunction of the 

installation and damage to the thermostat or 

air heater: 

• 

Use a cable with the following 

specifications: 

o

 

Signal cable. 

o

 

Shielded and twisted. 

o

 

Minimum dimensions: 1 

x 2 x Ø0,8 mm

2

o

 

Maximum length: 200 m. 

 Keep the thermostat cable 

separated from the mains cables. 

 

  

Connect the cable’s earth 

shield only to the earth terminal inside the air 

heater. Do not connect the other end of the 

cable’s earth shield

.

 

A cable with a thickness of less than 0.8mm will 

result in a poor signal. 

  

A cable that is not shielded 

and twisted may result in a disturbed 
communication in an EMC-unfriendly 
environment.

 

         L1   L2   L3    N 

11  12        4   5         6   7 

Содержание EH

Страница 1: ...INSTALLATION MANUAL AIR HEATER TYPE EH 1 Instruction manual AIR HEATER TYPE EH Version EH EN v00 02 ...

Страница 2: ...ing the air heater 6 4 2 1 Orientation 6 4 3 Electrical connection 8 4 3 1 Power supply 8 4 3 2 Fuse 8 4 4 Room thermostat 8 4 4 1 Installation requirements 8 4 4 2 Modulating room thermostat installation 9 4 4 3 Installation of multiple heaters on one control unit 9 5 Operating the air heater 11 5 1 Minimum firing time 11 5 2 Delta T regulation 11 5 2 1 Switch off delta T regulation 11 5 3 Summer...

Страница 3: ...on and void the warranty 2 Safety instructions Always follow the safety instructions in this chapter when installing using or performing maintenance on this air heater 2 1 Installation This air heater must be installed and maintained by an authorized qualified and competent installer using calibrated equipment This air heater must be installed and maintained in accordance with this manual national...

Страница 4: ...heater is not waterproof and has an IP00B classification Do not expose the air heater to rain spray or dripping water 2 4 Children and vulnerable users This air heater can be used by children aged 8 years and above and by persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they are supervised or instructed concerning use of the appliance in a safe wa...

Страница 5: ...39 8 Max el current per phase A 15 5 22 9 37 2 44 2 59 0 Air output warm m3 h 3 100 3 100 3 000 3 000 4 400 Throw horizontal max m 23 23 22 22 28 Electrical connection 50 Hz V 400V N 400V N 400V N 400V N 400V N Weight kg 25 26 28 30 34 Sound level 5 m dB A 55 58 55 58 55 58 55 58 57 60 3 2 Dimensions Figure 1 Dimensions of the EH 10 40 Type A B C D E F G H I J K EH 10 30 570 490 390 125 420 380 14...

Страница 6: ... of the Gas Safety regulations Electrical installation regulations and or other local regulations that may apply 4 2 Positioning the air heater Keep the following requirements in mind when choosing a location to install your air heater Never install an air heater close to flammable materials Keep sufficient distance between the heater and any obstructions This is both for safety reasons and to all...

Страница 7: ...on with threaded bars M10 The air heater is equipped with threaded sockets to suspend the unit see the dimension diagram in 3 2 Use the suspension kit that is compatible with your air heater The suspension kit is not delivered with the air heater Contact your supplier A B C D EH 10 30 795 380 280 745 EH 40 845 490 380 795 ...

Страница 8: ...at air can circulate around the thermostat Make sure the sun does not shine directly upon the thermostat Do not place the thermostat on a cold wall Place the thermostat on an inner wall free from draught Never place the thermostat within the throw of the heater Never mount the thermostat near the aerials of internal communication networks These emit radiation that can disturb the thermostat Keep s...

Страница 9: ...ure 9 This functionality does not apply to an ON OFF thermostat 1 Connect the two wires of the thermostat to terminals 4 and 5 of the first air heater 2 Connect the first air heater to the second air heater 3 Repeat for each subsequent air heater Figure 9 Connection of multiple air heaters to a modulating room thermostat Each air heater needs an unique number to be recognised by the room thermosta...

Страница 10: ...hree air heaters in a system If the J14 switch of more than one air heater is set to the same number the system will not work The air heater must be switched off when setting the switches Otherwise the settings will have no effect 1 2 3 4 5 6 7 8 ON 1 0 1 2 3 4 5 6 7 8 ON 1 0 S1 J14 1 2 3 4 5 6 7 8 ON 1 0 ...

Страница 11: ...can be set to run in the summer Follow the instructions in the user manual of the special Room thermostat 5 4 Overheating protection The air heater s heating elements are protected from excessive temperatures 5 4 1 Heating Elements An NTC sensor is located near or on the heating element This sensor monitors the heating element s temperature If the heating element becomes too hot this sensor will c...

Страница 12: ...or more than 24 uur 12 L 8 12 Internal error Internal error 13 L 15 Overheating Heating Element sensor is overheated 3 L 17 19 Internal error Internal error 13 L 25 Sensor Error Heating Element sensor failure 4 L 27 31 Internal error Internal error 13 L32 Sensor error Heating Element sensor faillure 4 L 33 38 Internal error Internal error 13 L 43 Overheat error Too many heating element sensor is o...

Страница 13: ...mespan This error will disappear after some time or if the main power is disconnected for a while Case 13 Internal error Isolate the electrical supply and reenergise If this does not help replace the burner control unit Case 16 Relay error Isolate the electrical supply Check if one of the relay has stuck while it was switched If yes replace the relays Reenergise the appliance Check if one of the r...

Страница 14: ...heater Focus on the following parts a Body b Fan blades and motor c Heating elements d Temperature sensor 5 Check if the wiring nuts and bolts are properly secured and tightened Some checks can only be performed when the heater is running Do the following 1 1 Reconnect the air heater to the power supply 2 Switch on the air heater 3 Check if the heater operates without problems See chapter 9 if any...

Страница 15: ...2 4 J12 2 J12 5 J12 3 J12 6 J8 1 J8 2 J6 7 J6 14 T1 J2 1 6 J1 1 J1 5 J1 2 J1 6 J1 3 J1 7 J1 4 J1 8 J3 2 J3 6 J3 1 J3 7 J3 3 J3 8 J3 4 J3 9 J3 5 J3 10 J4 2 J4 3 J4 5 J4 4 J4 1 J4 6 J5 1 J5 2 J5 4 J5 3 4 3 1 2 J25 LED RESET PE 5 4 J17 7 6 C4 C5 E1 P1 T1 T4 PE RT 14 13 N L K2 L A1 A2 K1 A1 A2 K1 Control unit 966 K2 K1 L triac 12 11 M2 7 4 L1 L3 L2 5 6 RT 3 x 400 V N 50 Hz 11 12 22 C PE N L1 L2 L3 L N...

Страница 16: ...X4204 2 Relay low IE5201 IE5201 IE5201 IE5201 IE5202 3 Relay high IE5201 IE5201 IE5202 IE5202 IE5202 4 Burner control unit GE5903 GE5903 GE5903 GE5903 GE5903 5 H Element 2 5 kW IE2510 IE2510 6 H Element 3 3 kW IE2512 IE2512 IE2512 IE2512 7 Sensor h element GY3932 GY3932 GY3932 GY3932 GY3932 8 Delta T sensor GY3931 GY3931 GY3931 GY3931 GY3931 1 3 2 4 5 6 8 7 ...

Страница 17: ...elevant EU directives being 2014 35 EU LVD relating to the electric safety of appliances 2014 30 EU EMC relating to the electromagnetic compatibility 2006 42 EG MD relating to the safety of machinery Goods should be installed and used in accordance with our instructions and with the applicable local and international rules Installation should be done by an authorized qualified and competent instal...

Отзывы: