background image

BattaMax User Manual  

Revision 3.0

 

 

Page 1 of 13 

windy

nation

 

10/04/2019 

 

 
 
 
 

 

 

 

Batta

Max 

Absorbent Glass Mat (AGM) – Sealed Lead Acid (SLA) Batteries 

BAT-RA12-033 
BAT-RA12-100 

 

User’s Manual

 

 

Содержание BattaMax BAT-RA12-033

Страница 1: ...BattaMax User Manual Revision 3 0 Page 1 of 13 windynation 10 04 2019 BattaMax Absorbent Glass Mat AGM Sealed Lead Acid SLA Batteries BAT RA12 033 BAT RA12 100 User s Manual...

Страница 2: ...ies Parallel Connection 7 4 Service and Maintenance 8 4 1 Charging 8 4 1 1 State of Charge SOC 8 4 1 2 Charge Characteristic Curve Standby Use 9 4 1 3 Temperature Compensation 9 4 2 Discharging 9 4 2...

Страница 3: ...nd servicing should be referred to qualified service personnel Remove all sources of power photovoltaic wind generator battery chargers etc before servicing or installing Battery Safety Warning Batter...

Страница 4: ...0hr 1 80V cell 25oC 35 Ah 106 Ah Nominal Capacity 10hr 1 80V cell 25oC 33 Ah 100 Ah Max Discharge Current 330A 5S 1000A 5S Internal Resistance 10 0m 5 0m Cycle Use 14 6 14 8V 25oC Temp Coefficient 4mV...

Страница 5: ...ures there is more chemical activity inside a battery than at lower temperatures The following chart shows the temperature effects to the battery capacity The following chart shows the temperature eff...

Страница 6: ...rminals and comes with the necessary bolts and washers to secure a cable connection Place battery connection cable lug not included over the threaded insert of the battery terminal ensuring that the c...

Страница 7: ...stem capacity Ah and the system voltage will remain unchanged For example if two 12V batteries with 50Ah of capacity are wired in series the resulting battery bank will be 12V of 100Ah 50Ah 50Ah 100Ah...

Страница 8: ...hat higher charge voltage to charge the battery quickly and safely Once the battery is fully charged a somewhat lower voltage is applied to maintain the battery in a fully charged state Important Batt...

Страница 9: ...y temperature The temperature should be adjusted by subtracting 0 004 volt per cell from the voltage reading for every 1 C above 25 C or adding 0 004 volt per cell for every 1 C below 25 C 4 2 DISCHAR...

Страница 10: ...5 36 0 6 68 20 9 3 50 10 8 1 65V cell 131 9 405 4 103 8 316 7 63 7 190 1 36 8 117 1 22 1 71 1 17 3 52 7 11 7 36 5 6 77 21 1 3 53 10 9 1 60V cell 136 9 407 0 107 0 318 5 65 6 191 5 37 9 118 0 22 8 71 7...

Страница 11: ...inter months it is critical that they are kept fully charged at all times 5 2 RECYCLING Batteries that have reached the end of their service life should be returned to a local or regional collection c...

Страница 12: ...e 1 year from the date the original purchaser Customer receives the Product the Warranty Period This warranty extends only to the original purchaser The Customer s sole and exclusive remedy and the en...

Страница 13: ...RPOSE WITH RESPECT TO ANY PRODUCTS PROVIDED BY WINDY NATION NO ORAL OR WRITTEN INFORMATION OR ADVICE GIVEN BY WINDY NATION ITS DEALERS DISTRIBUTORS AGENTS OR EMPLOYEES SHALL IN ANY WAY INCREASE THE SC...