Technical information

Page  2 of 2

Spindle actuator WMS 306  

Installation: 

The actuator can be installed in different ways.
The criteria to be taken into account include the 
different pressure and pulling forces to be applied or 
the varying fitting situations on site.
 
The actuator can be installed at the actuator end 
using a clamping ring and corresponding brackets, or 
using an eyebolt.

Ensure that all fastening and clamping screws are 
properly tightened. 

Settings and adjustments are made on site. 

To position the actuator, without power, manually 
adjust the spindle rod by turning it to it’s end position, 
please be aware the spindle rod can run in a further 
5mm when power is eventually applied.
If power is available, power the actuator to its end 
stop the position actuator to vent.

The electrical connection is to be made in accordance 
with the documentation for central control unit. 

Never 

access the actuator without the corresponding 

motor electronics.

Start-up: 

Ensure that the actuator motors are powered in a 
voltage range of 19-32V / DC and at a maximum 
residual ripple of 20%. 

The running direction of the actuators 
(OPEN/CLOSED) changes as the motor voltage 
polarity changes. 

Ensure that a min. 0.5 s delay is allowed between the 
OPEN and CLOSED commands

Only control the actuators in their self-locking mode. 
An activated CLOSED command must be followed by 
an OPEN command. 
Avoid retriggering of actuators which are run in the 
load switch-off mode. This could cause damage to the 
actuators. 

Ensure that the power supply to the central control 
unit on site is such that the start torque of the 
actuators can draw up to four times the overall power 
for a short period (min. 1 s) without the motor voltage 
dropping below 24V/DC. 

Note: 

Possible danger to persons caused by electric motor 
driven sash and frame. 

The high  forces occurring in the automatic mode 
can cause enjury. 
Actuators may extend into the room during opening, 
for this reason, care needs to be taken prior to 
starting up the actuators to exclude the risk of injury. 

With vents tilting inwards or outwards, the vent must 
be protected from dropping down once the actuator is 
unhooked (e.g. for window cleaning). 
For safety reasons we recommend the use of 
restrictors

In the event that vents or rooflights are subjected to 
high rain or wind loads , we recommend connecting 
the central control unit to a rain and wind sensor 
which will automatically close the vents. 

WSB 300 0011

Pushrod bracket

WSB 300 0010

Pushrod bracket

WSB 300 0012

Pushrod bracket

Wma 200770-0818                                   ©2007, 2018      ®WindowMaster is a registered trademark used under licence by WindowMaster Internationa

l A/S   

WSB 300 0004

bottom eyebolt

fastening

 

WSB 300 0001

Cla bracket

WSB 300 0002

Cla bracket

WSB 300 0003

Cla bracket

WindowMaster A/S 
 Skelstedet 13        
2950  Vedbæk
  Denmark
+45 45 67 03 00

Head office: 

CH: WindowMaster AG  
  +41 (0) 62 289 22 22

DE: WindowMaster GmbH  
+49 (0) 40 87 409 560

UK&IE: WindowMaster Control Systems Limited
+44 (0) 1536 614 070