WCC 3x0 Plus
DIP switches
Various wind/rain parameters and operating modes can be set by means of the installed DIP switches.
DIP switch settings for the wind speed
Test
Approx
.
3 m/s
Approx
4 m/s
Approx
6 m/s
Approx
8 m/s
Approx
10 m/s
Approx
12 m/s
Approx
14 m/s
Switch 1
off
on
off
on
off
on
off
on
Switch 2
off
off
on
on
off
off
on
on
Switch 3
off
off
off
off
on
on
on
on
Note
Factory setting = operation, meaning switch 1, 2, 3 and 6 = on and switch 4 and 5 = off.
Should there during installation be the need to disconnect the wind/rain drop out delay, set switch 1+2+3 = off (= Test).
Important! Once installation and star-up are completed, proceed with the wind speed setting required on site, meaning one or more of
the switches 1,2 or 3 MUST be on!
Remark: In the test setting, the activation and drop out delay is deactivated!
DIP switch settings
Switch setting OFF
Switch setting ON
Switch 4 = Wind activation delay
2 seconds
5 seconds
Switch 5 = Wind/rain drop out delay
10 minutes
20 minutes
Switch 6 = Monitoring
off
on
Information regarding switch 6:
Only the supply voltage (terminals 1+2) for the sensor is monitored.
The system will trip automatically in the event of a supply voltage failure.
Display:
Red steady light in the sensor LED = Sensor tripped by wind or rain.
Connection
Terminal 1 = Operating voltage AC/DC
Terminal 2 = Operating voltage AC/DC
Terminal 3 = Relay (arm)
Terminal 4 = Relay (N/C contact)
Terminal 5 = Relay (N/O contact)