DIP switches 

Various wind/rain parameters and operating modes can be set by means of the installed DIP switches. 
 

DIP switch settings for the wind speed 

 

 

Test 

Approx 

.

3 m/s 

Approx 

4 m/s 

Approx 

6 m/s 

Approx 

8 m/s 

Approx 

10 m/s 

Approx 

12 m/s 

Approx 

14 m/s 

Switch 1 

off 

on 

off 

on 

off 

on 

off 

on 

Switch 2 

off 

off 

on 

on 

off 

off 

on 

on 

Switch 3 

off 

off 

off 

off 

on 

on 

on 

on 

 
Note 

Factory setting = operation, meaning switch 1, 2, 3 and 6 = on and switch 4 and 5 = off. 
 
Should there during installation be the need to disconnect the wind/rain drop out delay, set switch 1+2+3 = off (= Test). 
 
Important! Once installation and star-up are completed, proceed with the wind speed setting required on site, meaning one or more of 
the switches 1,2 or 3 MUST be on! 
 
Remark: In the test setting, the activation and drop out delay is deactivated! 
 

DIP switch settings 

 

Switch setting OFF 

Switch setting ON 

Switch 4   =   Wind activation delay 

2 seconds 

5 seconds 

Switch 5   =   Wind/rain drop out delay 

10 minutes 

20 minutes 

Switch 6   =   Monitoring 

off 

on 

 
 

Information regarding switch 6: 

Only the supply voltage (terminals 1+2) for the sensor is monitored. 
The system will trip automatically in the event of a supply voltage failure.  
 

Display: 

Red steady light in the sensor LED = Sensor tripped by wind or rain. 

 
 

Connection 

 
Terminal 1  =  Operating voltage  AC/DC 
 
Terminal 2  =  Operating voltage  AC/DC 
 
Terminal 3  =  Relay (arm) 
 
Terminal 4  =  Relay (N/C contact) 
 
Terminal 5  =  Relay (N/O contact) 
 