Actuator type
Max number ± 24V actuators that may be connected to WCC 103 BT
WMB 801/802
3
WMB 811 / 812 / 815 / 816 / 817 / 818*
2
*with 2 locking actuators on the same motor line use: 1 x WMB 811 and 1 x WMB 812. 1 x WMB 815 and 1 x WMB 816 or 1 x WMB 817 and 1 x
WMB 818
3
Accessories
Accessories
Rain sensor
WLA 331
Rain / windspeed sensor
WLA 330
Comfort keypad, 1 window or 1 window group
WSK 110 0A0B
Comfort keypad, model FUGA, surface mounting (CH version)
WSK 300
Comfort keypad, model FUGA, surface mounting
WSK 103
Room thermostat: temperature
WLA 110
4
Technical data
Technical data
Output current
3A incl. load on X7 (max 0.5A)
Secondary voltage
Voltage
24V DC (±15%)
Resting potential with 230V AC without load
24V DC @ 20°C
Ripple with full load 150mVp-p
AUX
24V DC, 500mA
Motor groups / Motor lines
1 motor group with 1 motor line for ±24V standard actuators
Primary voltage
100-240 VAC 0.85A 50/60Hz
Power consumption
Idling < 0.5W
Full load 77 W
Inrush current on primary side
65A < 5ms w. 230V
Max. 6 x WCC 103 per 10A power supply group.
Circuit breaker “C” type.
±24V
Min. 500ms
LED signalling
2 green LEDs and 1 yellow indicate via blinking sequences failure and/or status of the
system and motor line. See paragraph on “Status and troubleshooting via LED” for a
detailed description and blinking sequences.
Connection cable
Actuators
Other components
flexible max. 6mm² / solid max. 10 mm²
min 0.2mm² / max. 1.5mm²
Operating conditions
-5°C - +45°C, for indoor mounting, the MotorController must not be covered
Max actuator activation duration (duty
cycle)
ED 40% (4 min. per 10 min.)
Material
Plastic
Colour
White (RAL 9016)
Size
215 x 206 x 37mm (W x H x D)
Weight
0.92kg
Protection class
IP 20
Safety class
I (with PE)
Delivery
Standard version:
MotorController with 1.2 m cable with Schuko plug
UK version:
MotorController with 1.2 m cable with Schuko plug and UK
network adapter
Note
We reserve the right to make technical changes