  To connect these units directly to an un-powered, 

  isolated construction site TemPower panel, have your 

  electrician connect to the control panel  using a 120/240 

  Volt, Anderson plug.

NOTE: 

To use the 120/240 Volt L14-30 receptacle to wire 

into a building, make sure the transfer switch is compatible 

for GFCI protected generators. 

2. If the generator set is connected to an existing 

 

distribution system, a fully isolated manual transfer switch 

  must be installed. The transfer switch must be compatible 

  with GFCI protected generators. WINCO recommends 

  Reliance manual transfer switches. The transfer switch 

  prevents damage to the generator and the other circuit 

  components if main line power is restored while the 

  generator is connected. Installing a transfer switch also 

  permits the use of normal fusing.

3. Many homes and construction sites are wired for at least 

  60 to 100 Amp entrance service, much greater than the 

  capacity of this portable generator. When installing the 

  generator at these sites, a secondary emergency 

  distribution panel may have to be installed. The 

  emergency distribution panel must be installed by a 

  licensed electrician according to all applicable codes. The 

  electrician will move the critical circuits to be powered 

  during the outage to the emergency panel. Keep in mind 

  only a limited amount of amperage is available from the 

  generator set. Some circuit breakers may still have to be 

  turned off to prevent an overload on the generator 

  during the initial start up. See the nameplate on your 

  generator for the amperage capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied to 

the generator will cause the generator to produce low 

voltage and may damage the engine generator set. It may 

also cause severe damage to the loads connected to the 

generator at that time. Improper loading of the generator 

set constitutes abuse and will not be covered by warranty.

Содержание WL22000VE

Страница 1: ...to contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCH...

Страница 2: ...ESHOOTING 17 RECEPTACLE WIRING DIAGRAM 18 WL22000VE B RECEPTACLE WIRING DIAGRAM 19 WL22000VE C CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important in...

Страница 3: ...mixed with fresh air A Operate only in well ventilated areas B Never operate indoors including attached garages C Never operate the unit in such a way as to allow exhaust gases to seep back into close...

Страница 4: ...r AME3 Part Number 16346 031 Rotor Resistance 9 743 Ohms 20 C Stator Resistance 0 366 Ohms 20 C Exciter Rotor Resistance 1 453 Ohms 20 C Exciter Stator Resistance 15 71 Ohms 20 C AVR DSR ENGINE Engine...

Страница 5: ...e performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle asse...

Страница 6: ...ess take about the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an...

Страница 7: ...re you check or add oil to the system The necessity of using the correct oil and keeping the crankcase full cannot be overemphasized Engine failures resulting from inadequate or improper lubricant are...

Страница 8: ...safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connections are clean an tight Reverse the sequenc...

Страница 9: ...asoline is blended to improve starting Do not use summer grade gasoline 2 HOT WEATHER A Use the proper oil for the temperature expected B Use only summer blended gasoline Using gasoline left over from...

Страница 10: ...f your generator is application dependent Carefully evaluate your planned use of your generator to understand which grounding you require If you are not sure what to do contact a competent professiona...

Страница 11: ...60 to 100 Amp entrance service much greater than the capacity of this portable generator When installing the generator at these sites a secondary emergency distribution panel may have to be installed...

Страница 12: ...T Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 120V 240V Half 3600 60 0 120V 240V Full 3510 58 5 120V 240V The speed of the engine was carefully adjusted at the f...

Страница 13: ...e YourGen meter will light up the oil icon and the word change will flash Once the oil has been changed press and hold the cycle button for approximately 5 seconds until the warning has been removed f...

Страница 14: ...e air filter and secure with the retainer D and fastener C 10 Install the cover B and secure with the fastener A Ensure the fastener is tight SPARK PLUG Replace annually or every 300 hours of operatio...

Страница 15: ...15 OPM 140 E CARBON CANISTER Designed to collect store and dispose of fuel vapors created in the fuel tank fuel system The canister should last the life of the unit as long as it stays dry...

Страница 16: ...sing damaged or cracked receptacles can be both dangerous to the operator and destructive to the equipment CLEANING Remove dirt and debris with a cloth or brush DO NOT use high pressure spray to clean...

Страница 17: ...stator Defective rotor field Defective AVR Circuit breaker trips Defective load Defective receptacle Excessive load Voltage too high Engine speed is too high Generator overheating Overloaded Insuffic...

Страница 18: ...18 OPM 140 E G1 N N N N N N N N N GND GND GND GND GND GND G2 G2 G2 G2 G2 G2 G2 G2 G2 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 RECEPTACLE WIRING DIAGRAM WL22000VE B...

Страница 19: ...19 OPM 140 E LOOM TO GENERATOR GREEN LEAD N N N N N N N N N GND GND GND GND GND GND G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2 G1 G1 G1 G1 G1 G1 G1 G1 RECEPTACLE WIRING DIAGRAM WL22000VE C...

Страница 20: ...medy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use and service will be re...