7
2015-00
60706-233
For your safety always connect the positive battery
cable to the “bat+” terminal first. Then connect the
negative battery cable to the “bat-” terminal. Make
sure all connections are clean and tight. Reverse
the sequence when disconnecting, disconnect the
negative cable first. These engines produce enough
direct current to keep a battery charged under nor-
mal operating conditions, but were not intended to
be used as a battery charger.
WARNING: PERSONAL INJURY
Lead acid batteries produce explosive hydrogen
gas when charging. Keep sparks, flames, and
burning cigarettes away from the battery. Ventilate
the area when charging or using the battery in an
enclosed space. Lead acid batteries contain sulfuric
acid, which causes severe burns. If acid contacts
eyes, skin or clothing, flush well with water. For con
-
tact with eyes, get immediate medical attention.
BATTERY CHARGING
Units equipped with electric start have a small fly
-
wheel charger built into the engine flywheel assem
-
bly for recharging the starting battery. This flywheel
charger generates a small AC current that passes
through a diode assembly to produce a DC charg-
ing current of about 1 to 3 AMPS. This circuit is not
designed to be used as a battery charging circuit to
recharge dead batteries.
OPTIONAL DOLLY KIT
An optional dolly kit is available for this generator.
The dolly kit comes with instructions and parts list.
After installing the dolly kit, file the instructions and
parts list in the back of this manual for future refer-
ence.
OIL ALERT SYSTEM
This WINCO Industrial generator is equipped with a
low oil shutdown system. This Honda engine uses
an float switch mounted inside the engine. If the oil
level drops below a certain point the low oil module
on the engine will shut it down. This low oil warning
system will automatically stop the engine before the
oil level reaches a critical danger point. This feature
is designed to prevent costly repairs and downtime.
CAUTION: EQUIPMENT DAMAGE
Allowing the engine to shutdown repeatedly on
low oil level may cause excessive wear which can
be cumulative.
INITIAL START UP
The throttle control on these generators is preset
and locked to operate at 3600 RPM (nominal) with
no load speed set at 3690 RPM. Only a trained
service technician should be allowed to adjust this
speed setting.
NOTICE: ENGINE START LOCKOUT
This unit
will not start
if it is low on oil. The lu-
bricating oil level must be at the
full
mark before the
engine will start and run.
BASIC OPERATION
ELECTRIC STARTING
If the engine is cold and stiff or if the battery is not
fully charged, starting can be made easier by slowly
hand cranking the engine through the compres-
sion stroke before pushing the starter switch. This
permits the starter to gain momentum before the
heavy load of the compression stroke occurs. This
minimizes the drain on the battery and improves the
possibility of starting under such adverse conditions.
Always keep the battery charged, especially during
cold weather operation.
1. Check oil level, refill as needed
2. Turn on the fuel supply. Ref “A” Lever pointing
up is on, lever pointing down is off.
A