THE GENERATOR IS ON STANDBY, AND MUST ISOLATE
THE COMMERCIAL POWER LINES FROM THE LOAD AND
THE GENERATOR WHEN THE GENERATOR IS SUPPLYING
POWER. SEE FIGURE 5.

Operation

OUTPUT POWER AVAILABLE AND LOAD DETERMINATION

Before using the generator, read and understand the following
information.

Generator output current (amperage) is internally limited by
three circuit breakers. If too much demand is placed on a
generator output (if you try to drive too many motors with it, for
example), one of the circuit breakers will trip, cutting off the
output in order to protect the generator.

A 15 amp push-to-reset circuit breaker protects the 120V
duplex receptacle output circuit. 15 amps is the total limit for
both outputs of the duplex receptacle. (Not available on the
480 volt three phase generators.)

A 50 amp two pole switch type circuit breaker protects the
240V receptacle output circuit. (Not available on  the 480 volt
three phase generators.)

A large two pole (three pole for three phase) switch type main
circuit breaker protects the generator windings and output
circuits, including the load disconnect receptacle. (On the
W135PTOS,  W145PTOT and the 150PTOS you will connect
your power output leads directly to the mainline circuit
breaker.)

To aid in determining how much load can be applied to the
generator, and how it should be distributed among the
generator output receptacles, the following formulas may be
useful. Get load voltage, current, and wattage from the
nameplates on the equipment in the load.

(Load Current, in amps) x (Load Voltage) = (Load Wattage)

AMPS X VOLTS = WATTS
WATT/1000 = kW

(Load Current in amps) = (Load Wattage)/(Load Voltage)

Example:
250W, 120V floodlight load = 250W/120V= 2 amps (parrots.)

NOTE:
Electric motors require much more current to start than to run.
Commonly, the current rating given on a motor nameplate is
the full load (running) current required by the motor, not its
starting current, which is a lot higher. Motor starting current
requirements vary greatly, by motor size and type. Repulsion-
induction type motors are the easiest to start, typically using 1
1/2 to 2 1/2 times as much current to start as to run; capacitor
type motors usually require 2 to 4 times as much current to
start as to run; split-phase type motors are the hardest to start,
normally using 5 to 7 times as much current to start as to run.

MOTOR LOAD

SINGLE PHASE

THREE PHASE

Motor

Amps

Amps

Amps

Amps

Horsepower

115V

230V

208

240

(Running Amps)

(Running Amps)

1/4

5.8

2.9

1/3

7.2

3.6

1/2

9.8

4.9

2.3

2.0

3/4

13.8

6.9

3.2

2.8

1

16

8

4.15

3.6

1-1/2

20

10

6.0

5.2

2

24

12

7.8

6.8

3

34

17

11

9.6

5

56

28

17.5

15.2

7-1/2

80

40

25

22

10

100

50

32

28

20

62

54

40

120

104

Compiled from N.E.C. manual.

To use the full capacity of the generator without tripping its
circuit breaker(s), start the motors in the load one at a time,
highest starting current motor first, next highest second, etc.
Use the preceding table as a source of general information
about motor running current requirements. For more specific
information, see motor nameplate or motor manufacturer’s
catalog.

PRE-START CHECKS

WARNING:  Personal Injury

When working on or around these generators, do not wear
loose fitting clothing or any articles that may get caught in
moving parts.

1. Visually inspect the generator. Check for:

a. Correct mounting
b. Physical damage
c. Debris in cooling vents and screens (could
cause generator to overheat).

IMPORTANT: The manufacturer recommends that, if the
generator has been stored for any length of time, before using
it, the operator remove the control box cover and cooling fan
screen, then inspect the generator for rodent nests or other
objects that could cause generator binding and/or
overheating. See “Cleaning” portion of Maintenance section.

2. Check gear case oil level. (See Figure 6.) Case should be
filled with oil to plug marked “OIL LEVEL.” Fill or remove oil as
required.

NOTE: EITHER TOO LITTLE OR TOO MUCH OIL CAN HARM
THE EQUIPMENT.

See “Lubrication” portion of Maintenance for oil specifications.

Содержание W100PTOS

Страница 1: ...60706 160 W100PTOS W105PTOT W135PTOS W145PTOT W150PTOS Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR ...

Страница 2: ...TION 5 Pre Start Checks 5 Starting Procedure 6 Stopping 6 MAINTENANCE 7 Lubrication 7 Cleaning 8 Storage 8 TroubleShootingTable 8 GENERATORCONNECTIONS 120 240 Volt Single Phase 10 120 240 Volt Three Phase 10 120 208 Volt Three Phase 11 277 480 Volt Three Phase 11 GENERATORRECEPTACLEPANELS 12 Convenience Receptacle Wiring 13 36MONTHWARRANTY 14 PROPER USE AND INSTALLATION You must be sure your new g...

Страница 3: ...n and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring but continual e...

Страница 4: ...ay the subpack carton with the large carton 4 Open the subpack carton and make sure it contains a Generator instruction manual b Load disconnect plug disassembled in bag 5 Remove the four bolts which hold down the generator feet to the pallet 6 Lift the generator from the pallet by means of the lifting eye on the top of the generator 7 Inspect the generator carefully for freight loss or damage If ...

Страница 5: ...less than 15 degrees during generator operation even though the mechanical design of the tumbling bar would allow greater misalignment The following wire sizes are recommended for each unit Generator Size Model AWG Insulation W100PTOS 4 0 Neoprene THHN W105PTOT 4 0 Neoprene THHN W135PTOS 350MCM THHN NO Plug Provided W145PTOT 4 0 THHN NO Plug Provided W150PTOS 500MCM THHN NO Plug Provided WARNING E...

Страница 6: ...ns should install electrical wiring Wiring must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrical Code DANGER PERSONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE DISCONNECT MUST ISOLATE ...

Страница 7: ... its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2 1 2 times as much current to start as to run capacitor type motors usually require 2 to 4 times as much current to start as to run split phase type motors are the hardest to start normally using 5 to ...

Страница 8: ...TE EquipmentDamage If the load includes motors turn them on one at a time highest starting current motor first next highest second etc Adjust engine throttle to keep generator output under load at 60 Hz If the engine is equipped a with governor it may automatically adjust the throttle as the load changes and keep the generator output at the proper level However some governors are not sensitive eno...

Страница 9: ...he generator The drive shaft tumbling bar requires greasing Keep the universal joints in the coupling shaft free from grease and dirt buildup NOTE Do not over lubricate the universal joints See Figure 8 for recommended lubrication schedule for the coupling shaft Check the generator gear case oil level before each use of the generator Maintain the oil level at oil level plug height Figure 6 illustr...

Страница 10: ...rloaded 2 Reduce load if it is higher than the rated capacity of the generator See generator nameplate 3 Inadequate engine horsepower 3 Generator requires 2 HP 1000 watts output Obtain larger engine if necessary 4 Defective or mis adjusted AVR 4 Repair adjust or replace as required 5 Replace the oil level check plug 6 Replace the breather CLEANING INSPECTINGTHEGENERATOR Use a vacuum cleaner or dry...

Страница 11: ...er take off misalignment 1 Correct misalignment It should be less than 15 degrees vibration excessive 2 Loose mounting nuts and bolts 2 Tighten mounting nuts and bolts repair hold down stud or hold down studs mountings 3 Universal joints in coupling 3 Repair or replace defective parts shaft worn or dry 4 Defective bearings 4 Check for possible causes Replace defective bearings Generator 1 Poor ven...

Страница 12: ...Page 10 60706 160 3117 20 GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE ...

Страница 13: ...Page 11 60706 160 3117 20 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE ...

Страница 14: ...Page 12 60706 160 3117 20 GENERATOR RECEPTACLE PANEL W105PTOT 4 W105PTOT 17 GENERATOR RECEPTACLE PANEL W100PTOS 3 GENERATOR RECEPTACLE PANEL W105PTOT 18 ...

Страница 15: ...60 3117 20 GENERATOR RECEPTACLE PANEL ON MODELS W135PTOS 3 W145PTOT 4 W145PTOT 17 W150PTOS 3 GENERATOR RECEPTACLE PANEL ON MODEL W145PTOT 18 GENERATOR CONVENIENCE RECEPTACLE WIRING ON ALL MODELS EXCEPT 480 VOLT UNITS ...

Страница 16: ...mitationsonthedurationofanimpliedwarranty andsomestatesdonotallow the exclusion or limitation of incidental or consequential damages so that above limitation or exclusion may notapplytoyou Thiswarranty givesyouspecificlegalrights youmayhaveother rights which vary from state to state This warranty is limited to bench labor and parts only no allowance will be made for travel time or removalandreinst...

Отзывы: