    .  Turn on the preferred source (utility) circuit 

breaker.  The utility source acceptable light should 

now come on as well as the transfer switch on utility 

light.  If these lights fail to come on recheck your 

incoming power to insure you have 240 volts nomi-

nal.  If not, troubleshoot your utility source before 

continuing.

     ******************

*****  WARNING  *****

     ******************

PERSONAL INJURY HAZARD - Install front cover 

in transfer switch before operation.  An electrical sys-

tem fault could cause a flash and severe personal 

injury.

    

2.  Press and release the 

Auto button

 on the 

engine control module (ECM).  The auto mode icon 

will appear on the screen.  The unit is now ready to 

be operated from the Automatic Transfer Switch.

    .  Turn on the altenate source (generator) curcuit 

breaker.

There are two ways to test your transfer switch 

operation:  WITHOUT a load transfer or WITH a 

load transfer.

WITHOUT load transfer (normal exercise)

    .  Press and release the 

Push to Test 

button.  

The generator set should start immediately.  About 

5 seconds the generator (alternate source) accept-

able light comes on and stays on.  

    2.  The generator set runs for 20 minutes.  The 

Transfer Switch does not transfer the load to the 

generator set. The 

Transfer Switch 

on utility (pre-

ferred source) light stays on.

    .  To bypass the time delay or cancel the test, 

press and release the 

Push to Test 

button again.

    4.  The generator set stops and the 

Generator 

acceptacle light goes off.

WITH Load Transfer

    .  Press and hold the 

Push to Test 

button until 

the generator (alternate source) acceptable light 

comes on and stays on.  Then release the button.  

This will start up your generator set.

This light indicates that the generator is running and 

the output voltage and frequency are within accept-

able limits.  Under normal conditions this light should 

come on in 5 to 0 seconds.  If the light does not 

come on and stay on a malfunction has occurred.  

Either the unit didn’t start or the voltage or frequency 

is incorrect.  Correct the problem before continuing.

    2.  About 5 seconds after the generator (alter-

nate source) acceptable light comes on, the auto-

matic transfer switch should transfer the load from 

the utility to the generator.  At that time the Transfer 

Switch

 

generator acceptable light should come on.

    .  The generator will stay connected to the load 

for about 5 minutes at which time the transfer switch 

will transfer the load back to the utility.  At the time it 

transfers back to utility the Transfer Switch on Utility 

light should come on and the Transfer Switch on 

generator light should go out.  To bypass this five 

minute time delay you can press and release the 

Push to Test

 button again at any time.

    4.  After the load retransfer to the utility, the gen-

erator will continue to run for about  minute (without 

a load) and then shut down.  The Generator accept-

able light will go off indicating the generator set has 

shut down.  

This completes the functional test of the transfer 

switch and the generator set.  If you want the gen-

erator to automatically start press the 

Auto 

button 

on the engine control module of the generator set.  If 

you have additional work to do or don’t want to leave 

the engine generator set in the automatic start mode 

press and release the 

stop/reset

 button on the gen-

erator set.  In the off mode the engine generator set 

will not start or run automatically.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to 

automatically exercise the generator for 20 minutes 

once every 4 days.

In order to set and test the exercise circuit the 

engine control module must be set in the auto 

mode.

SETTING THE EXERCISER CIRCUIT

Press and release the 

Automatic Generator Exer-

ciser 

button.  After about 8 seconds the exerciser 

light flashes 4 times to indicate that the exerciser 

circuit has been set.  The number of flashes indi-

cates the number of days until the next exercise 

period.  This 20 minute period will occur at approxi-

mately the same time of the day the button was 

pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the 

Automatic Generator Exerciser 

button until the light goes off, the light flashes then 

goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the 

Automatic Generator Exerciser 

button until the light goes off, the light flashes then 

goes off.  After about 8 seconds the exerciser light 

flashes fourteen times to indicate that the exerciser 

circuit has be re-enabled.

     ******************

*****  WARNING  *****

     ******************

WITH A TOTAL POWER FAILURE (UTILITY 

POWER FAILS AND THE GENERATOR FAILS TO 

START AND RUN) THE EXERCISER MUST BE 

RESET AFTER THE POWER IS RESTORED.

CLEARING AN “ERROR” CODE 

An error codes occurs on the ASCO control board if 

the generator set fails to start or there is some other 

malfunction.  BOTH Transfer Switch lights will be 

blinking together.  The Automatic Generator Exer-

ciser light will be blinking a number of times then 

pause.  This number gives the error code reason 

from page 8 of the ASCO 65 owner’s manual.  To 

clear this code press and release the 

Push to Test

 

button once.  Then troubleshoot the problem accord-

ing to the ASCO 65 owner’s manual.

This completes your installation and unit testing.  

ALWAYS leave the system in automatic mode unless 

servicing the unit.  For automatic operation, the auto 

mode icon must be displayed on the engine control 

module.

DSE 3110 ENGINE CONTROL

PROTECTIONS

When an alarm is present, the Common alarm LED 

if configured will illuminate.  

The LCD display will 

show an icon to indicate the fault.

WARNINGS

Warnings are non-critical alarm conditions and do 

not affect the operation of the generator system, 

they serve to draw the operators attention to an un-

desireable condition.  The icon will appear steady in 

the display.  Warning alarms are self-resetting when 

the fault condition is removed.  

SHUTDOWNS

Shutdowns are critical alarm conditions that stop the 

engine and draw the operator’s attention to an un-

desirable condition.  Shutdown alarms are latching.  

The fault must be removed and the STOP/RESET 

button pressed to reset the module.  

The icon will 

appear flashing in the display.

MODULE DISPLAY

TIMER ICON

When the module is controlling the engine (start-

ing and stopping) an animated timer icon will be 

displayed in the icon area to indicate that a timer is 

active, for example cranking time, crank rest, etc.

STOPPED ICON

When there are no alarms present, an icon will be 

displayed to indicate the engine is stopped and what 

mode the unit is in.

  Stop Mode           Auto Mode            Manual Mode

RUNNING ICON

When there are no alarms present, an animated icon 

is displayed to indicate the engine is running.

USB ICON

When a USB connection is made to the module the 

USB icon is displayed.

MEMORY CORRUPTION

If either the config file or engine file becomes cor-

rupted the unit will display the following icon.

 

Содержание ULPSS12H2E

Страница 1: ... 11075 01 60706 209 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS12H2W E ...

Страница 2: ...ous situ ation which if not avoided will result in death or serious injury This signal word is to be limited to the most extreme situations WARNING WARNING inducates a potentially hazardous situ ation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a potentially hazardous situ ation which if not avoided may result in minor or moderate injury It may also be us...

Страница 3: ...led These packaged standby systems consist ot two major components 1 AUTOMATIC TRANSFER SWITCH A wall mounted ASCO 165 Automatic Transfer Switch ATS designed for inside installation The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry necessary to start and stop the...

Страница 4: ... line that is required to supply the engine with a constant fuel pressure and volume LIQUID PROPANE VAPOR LP Refer to the tables below for fuel line size and rec ommended tank size For distances of 100 feet or over a two regulator fuel system is recommended This is accomplished by installing a primary regula tor at the tank which will reduce the tank pressure down to 10 to 15 lbs A low pressure re...

Страница 5: ...other metal objects 2 Use tools with insulated handles 3 Check both the battery cable ends and the bat tery posts to be sure they are free of corrosion 4 Always connect the battery positive cable first and then connect the battery negative cable When removing the battery cables from the bat tery reverse the procedure disconnect the nega tive cable first and then the positive cable 5 Be sure all co...

Страница 6: ...100 amps If you have a 125 150 200 amp or larger system and want to use a 100 amp transfer switch you will not be able to transfer the complete electrical system In this case it will be necessary to install a secondary emergency distribution panel NOTE THE MAXIMUM OUT PUT OF THE GENERATOR IS 50 AMPS AT 240 VOLTS AC ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD W...

Страница 7: ...ected to the terminals L2 L6 The normal line power terminals in the ATS are marked PREFERRED L1 L5 The hot line power leads are L1 and L3 from your normal power supply are connected to terminals L1 and L5 The load terminals in the ATS are marked LOAD L3 L7 The leads to the load distribution panel are connected to terminals L3 L7 The neutral leads from all three locations are con nected to the isol...

Страница 8: ... off mode the engine generator set will not start or run automatically GENERATOR EXERCISER CIRCUIT The automatic generator exerciser is configured to automatically exercise the generator for 20 minutes once every 14 days In order to set and test the exercise circuit the engine control module must be set in the auto mode SETTING THE EXERCISER CIRCUIT Press and release the Automatic Generator Exer c...

Страница 9: ...ompatible engine ECU PAGE Pressing this button scrolls the display to show the various instruments FRONT PANEL CONFIGURATION 1 2 3 4 This configuration mode allows the operator limited customizing of the way the module operates Use the module s navigation buttons to traverse the menu and make value changes to the parameters ACCEPT button 2 NEXT PAGE button DECREASE VALUE NEXT ITEM 4 INCREASE VALUE...

Страница 10: ...larger are rec ommended In addition you should consider install ing an oil heater kit and a battery warmer for reliable starting during cold weather MAINTENANCE LOG DATE WORK PERFORMED 225 S CORDOVA AVE LECENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 DESCRIPTION AUXILIARY INPUTS Auxiliary inputs can be user configured and will display the message as written by the user FAIL TO START The e...

Страница 11: ...11075 01 20 60706 209 21 11075 01 60706 209 ENGINE GENERATOR SET LAYOUT ULPSS12H2W E ENGINE GENERATOR SET PAD LAYOUT ...

Страница 12: ... in the bottom of air cleaner from crankcase breather 10 Defective starter fuel solenoid relay s ENGINE STARTS AND THEN STOPS AND FAULT ICON COMES ON 1 Engine is low on oil 2 No AC output from generator to engage stop crank circuit ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS 1 Insufficient fuel volume getting to the unit a Fuel line too small b Low fuel pressure 2 AC short circuit 3 Wiring to...

Страница 13: ...and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations may not app...

Отзывы: