![Winco DR2014 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/winco/dr2014/dr2014_installation-and-operators-manual_984695009.webp)
9
OPM-109
REV A
D.C. ELECTRICAL CONNECTIONS
All DC connections are completed on the terminal strip just below
the engine control. All DC connection must be separate conduit. You
cannot mix AC and DC leads at the same conduit.
CONNECTION BOX TERMINALS
Wire size requirements for each of the connections may vary but
terminal lugs should be used for all connections. Torque spec for
terminal lugs is 9 in. lbs.
A. CUSTOMER REMOTE START CONNECTION TERMINALS.
The two remote start leads from the Automatic Transfer Switch are
connected to the two terminals marked GROUND & START. The WIRE
in terminal GROUND is battery negative and the wire in the terminal
13
5060-00
60708-165
A -
C
ustomer
R
emote
Start
C
O
N
N
EC
TIO
N
S T
ER
M
IN
A
LS
.
The
two remote start leads from the
Automatic
Transfer Switch are
connected to the two terminals marked GROUND & ST
AR
T.
The
wire in terminal GROUND is Battery Negative and the wire in the
terminal labeled ST
AR
T is your Remote Start lead. Closing these
two leads together will signal the DSE 7310 to go into an auto-
start mode and start up the engine generator
.
Depending on the distance, 14 to 16 gauge stranded wire
should be used. It is suggested that these wires be labeled S1
JURXQGDQG6VWDUW
The terminal blocks are designed to
use terminal lugs on all wires and the screws should be torqued
to 9.6 in. lbs.
1RWH
$Q\UHOD\FORVXUHFDQEHXVHGWRVWDUWDQGVWRSWKLV
JHQHUDWRU
$VORQJDVWKHFRQWDFWVWD\VFORVHGWKHHQJLQH
JHQHUDWRUVHWZLOOFRQWLQXHWRUXQ2QFHWKHUHOD\LVRSHQHG
WKHXQLWZLOOVKXWGRZQDQGUHPDLQLQWKHVWDQGE\PRGHXQWLO
WKHUHPRWHVWDUWUHOD\LVFORVHGDJDLQ
B - EST
OP- & EST
OP+.
Remote Emergency Stop terminals.
These two terminals are shipped with a jumper installed. If you
r
application requires the installation of a Remote Emergency
Stop switch, remove the jumper and wire your switch to these
terminals.
This unit will not start and run without either the
jumper installed or a remote N/C switch installed.
.
C. - Battery Charger Failure.
Battery charger failure relay input
from remote battery charger to DSE7310 controller
.
D - Remote Display Panel Interface T
erminals.
These
interface terminals are prewired to allow for the connection of
a
remote display
.
This display allows for the remote annunciatio
n
of alarms at a location such as a nurses station or a control
room.
This display can used to meet the remote annunciation
requirements of NFP
A 1
10 standards. (
This feature meets the
annunciation requirements in applications requiring NFP
A1
10
level one protection.)
DC Interconnections to the
Automatic T
ransfer Switch
*************
***** W
ARNING *****
*************
%HVXUH(QJLQH*HQHUDWRULVLQWKH³2))´SRVLWLRQEHIRUH
you make any DC interconnections.
*******CAUTION******
1HYHUUXQWKH
$&DQG'&ZLULQJLQWKHVDPHFRQGXLW
ASCO 185 UL
SWITCH
<RXU'&FRQQHFWLRQSRLQWVLQWKH
$6&2
$76DUH
WHUPLQDOV³´DQG³RQWKHLQWHUIDFHWHUPLQDOEORFN
ASCO 300 UL
SWITCH
Your DC connection points in the
ASCO 300
ATS are terminals
³´DQG³´'HSHQGLQJRQWKHVL]HRIWKHVZLWFKWKH\DUH
located in dif
ferent locations.
TB7
rem
ovab
le
te
rmin
al
b
lock
TB7
–4
,TB7
–5
,TB7
–6
1
2
3
4
5
6
7
8
9
Figure
4.
TB7
generato
r
starti
ng
co
ntact
termi
nal
s.
Ta
b
le
A
.
G
en
er
ato
r
S
ta
rt
C
on
ne
cti
on
s
W
h
en
th
e
U
tili
ty
fa
ils
Te
rm
in
als
o
n
C
on
trolle
r
con
ta
ct
close
s
TB7
–4
and
TB7
–5
co
nt
ac
to
pe
ns
TB7
–5
and
TB7
–6
A
B
C
D
F: NEUTRAL TO GROUND LEAD LUG:
This lug is provided on the neutral terminal block to allow you to run
a neutral to ground lead if you are using the generator in a stand
alone application. This would be an application where there is not a
distribution panel and no other ground to neutral bond in the wiring
system. If a grounding wire is attached here, remove the floating
neutral label in the panel. This will not be used when you are wiring a
generator and transfer switch into an existing power system.
WARNING:
A mainline circuit breaker has been provided inside the generator
housing. During all wiring installations, make sure the breaker is in the
OFF position and the generator operating switch is in the OFF position.
WARNING: EQUIPMENT DAMAGE:
When installing a three-phase 240 Volt system, be sure you know
which lead is the high voltage “wild” leg (208 Volt line to neutral). The
generator normally carries the high voltage on the G2 lead.
All wires should be installed in rigid or flexible conduit (knockouts are
provided in the control box).
GROUNDING
A grounding lug has been provided on the engine generator set and
the generator set must be properly grounded to good earth ground.
Generally an 8 foot copper rod driven into the earth wil provide a proper
earth ground.
labeled START is your remote start lead. Closing these two leads
together will signal the DSE7310 to go into an autostart mode and start
up the generator.
Depending on the distance, 14 to 16 gauge standard wire should be
used. It is suggested that these wires be labeled S1 (ground) and S2
(start). The terminal blocks are designed to use terminal lugs on all
wires and the screws should be torqued to 9.6 in. lbs.
Note: Any relay closure can be used to start and stop this generator.
As long as the contact stays closed, the generator set will continue to
run. Once the relay is opened, the unit will shut down and remain on
standby mode until the remote start relay is closed again.
B. ESTOP - & ESTOP +.
These two terminals are shipped with a jumper installed. If your
application requires the installation of a Remote Emergency Stop
switch, remove the jumper and wire your switch to these terminals. This
unit will not start and run without the jumper installed or a remote N/C
switch installed.
C. BATTERY CHARGER FAILURE.
Battery charger failure relay input from remote battery charger to
DSE7310 controller.
D. REMOTE DISPLAY PANEL INTERFACE TERMINALS.
These interface terminals are prewired to allow for the connection os
a remote display. This display allows for the remote annunciation of
alarms at a location such as a nurce’s station or a control room. This
display can be used to meet the remote annunciation requirements
of the NFPA 110 standards (this feature meets the annunciation
requirements in applications requiring NFPA 110 level on protection).
DC INTERCONNECTIONS TO THE ATS
WARNING:
Be sure Engine/Generator is in the OFF position before you make any
DC interconnections.
CAUTION:
Never run the AC and DC wiring in the same conduit.
ASCO 185 UL SWITCH
13
5060-00
60708-165
A - Customer Remote Start CONNECTIONS TERMINALS.
The
two remote start leads from the Automatic Transfer Switch are
connected to the two terminals marked GROUND & START. The
wire in terminal GROUND is Battery Negative and the wire in the
terminal labeled START is your Remote Start lead. Closing these
two leads together will signal the DSE 7310 to go into an auto-
start mode and start up the engine generator.
Depending on the distance, 14 to 16 gauge stranded wire
should be used. It is suggested that these wires be labeled S1
JURXQGDQG6VWDUW
The terminal blocks are designed to
use terminal lugs on all wires and the screws should be torqued
to 9.6 in. lbs.
1RWH$Q\UHOD\FORVXUHFDQEHXVHGWRVWDUWDQGVWRSWKLV
JHQHUDWRU$VORQJDVWKHFRQWDFWVWD\VFORVHGWKHHQJLQH
JHQHUDWRUVHWZLOOFRQWLQXHWRUXQ2QFHWKHUHOD\LVRSHQHG
WKHXQLWZLOOVKXWGRZQDQGUHPDLQLQWKHVWDQGE\PRGHXQWLO
WKHUHPRWHVWDUWUHOD\LVFORVHGDJDLQ
B - ESTOP- & ESTOP+.
Remote Emergency Stop terminals.
These two terminals are shipped with a jumper installed. If your
application requires the installation of a Remote Emergency
Stop switch, remove the jumper and wire your switch to these
terminals.
This unit will not start and run without either the
jumper installed or a remote N/C switch installed.
.
C. - Battery Charger Failure.
Battery charger failure relay input
from remote battery charger to DSE7310 controller.
D - Remote Display Panel Interface Terminals.
These
interface terminals are prewired to allow for the connection of a
remote display. This display allows for the remote annunciation
of alarms at a location such as a nurses station or a control
room. This display can used to meet the remote annunciation
requirements of NFPA 110 standards. (
This feature meets the
annunciation requirements in applications requiring NFPA110
level one protection.)
DC Interconnections to the
Automatic Transfer Switch
*************
***** WARNING *****
*************
%HVXUH(QJLQH*HQHUDWRULVLQWKH³2))´SRVLWLRQEHIRUH
you make any DC interconnections.
*******CAUTION******
1HYHUUXQWKH$&DQG'&ZLULQJLQWKHVDPHFRQGXLW
ASCO 185 UL SWITCH
<RXU'&FRQQHFWLRQSRLQWVLQWKH$6&2$76DUH
WHUPLQDOV³´DQG³RQWKHLQWHUIDFHWHUPLQDOEORFN
ASCO 300 UL SWITCH
Your DC connection points in the ASCO 300 ATS are terminals
³´DQG³´'HSHQGLQJRQWKHVL]HRIWKHVZLWFKWKH\DUH
located in different locations.
TB7
removable
terminal block
TB7–4, TB7–5, TB7–6
1 2 3 4 5 6 7 8 9
Figure 4. TB7 generator starting contact terminals.
Table A. Generator Start Connections
When the Utility fails
Terminals on Controller
contact closes
TB7–4 and TB7–5
contact opens
TB7–5 and TB7–6
TB7 Generator starting contact terminals