Washbasin fitting
WimTec SMART
Hy
Plus
25
EN
SMART
Hy
Plus
Function description
Intelligent stagnation flush:
DIP switch 4
ON
OFF
2 3 4 5 6
1
0,5 - 24 h
10 - 180 s
um 07:00 Uhr
um 07:00 Uhr
Serves to flush water supply lines in order to remove stagnant
water that accumulates during longer periods of disuse.
‘ON’ position =
Intelligent stagnation flush is enabled (default setting).
‘OFF’ position =
Intelligent stagnation flush is disabled.
Flushing interval
Specifies the time span between the
stagnation flushing processes.
Adjustable from 0,5 to 24 h via the
interval control (see page 20).
Intelligent stagnation flush
If the fitting has not been in use at least for
the minimum flushing duration, an automa-
tic flush for the remaining duration will be
actuated.
Otherwise no automatic flushing will occur.
Minimum flushing duration
Specifies the minumum waterflow
duration within the set time interval.
Adjustable from 10 to 180 s via the
minimum flushing duration control
(see page 20).
um 07:00 Uhr
um 07:00 Uhr
Tip
i
Minimum flushing
duration visualizati-
on see page 27!