7 Commissioning

Commissioning only by qualified technicians.

7.1 Venting

• Fill and vent the system correctly.
If the pump does not vent automatically:
• Activate the pump venting function via the operating 

button: press and hold for 3 seconds, then release.

The pump venting function is initiated and 

lasts 10 minutes.

The top and bottom LED rows flash in turn at 1 second 

intervals.

• To cancel, press and hold the operating button 

for 3 seconds.

7.2 Setting the control mode

Select control mode

The LED selection of control modes and corresponding 

pump curves takes place in clockwise succession.
• Press the operating button briefly (approx. 1 second).

LEDs display the set control mode and pump curve.

The following shows the various possible settings, 

beginning with the factory setting (constant speed / 

pump curve III):

sec

3

min

10

 

NOTICE

After venting, the LED display shows the 

previously set values of the pump. 

Содержание Wilo-Para 15-130/7-50/SC-12/I

Страница 1: ...au und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service Wilo Para 4 530831 Ed 01 2017 08 Wilo APPLIES TO EUROPEAN DIRECTIVE FOR ENERGY RELATED PR...

Страница 2: ...Fig 1 12 Para iPWM 11 8 1 2 3 4 5 8 9 10 7 Para SC 6...

Страница 3: ...Fig 2 Fig 3 a b Fig 4 Fig 5a Fig 5b 1 2 PE N L...

Страница 4: ...Fig 5c Fig 5d Fig 5e Fig 5f Fig 6...

Страница 5: ...rheits hinweise in den weiteren Kapiteln beachten Missachtung dieser Betriebsanleitung hat eine Gef hrdung f r Personen die Umwelt und des Produkts zur Folge Dies f hrt zum Verlust jeglicher Schadener...

Страница 6: ...l muss In den lokal g ltigen Unfallverh tungsvorschriften unterrichtet sein Die Einbau und Betriebsanleitung gelesen und ver standen haben Das Personal muss die folgenden Qualifikationen haben Elektri...

Страница 7: ...erstrom Schutz schalter RCD abgesichert werden Das Produkt muss geerdet werden Defekte Kabel umgehend durch eine Elektrofachkraft austauschen lassen Niemals das Regelmodul ffnen und niemals Bedienelem...

Страница 8: ...ckeranschluss Funktion Hocheffizienz Umw lzpumpe f r Warmwasser Hei zungssysteme mit integrierter Differenzdruck Regelung Regelungsart und F rderh he Differenz druck lassen sich einstellen Der Differe...

Страница 9: ...I II III innerhalb der Regelungsart Anzeigekombinationen der LEDs w hrend der Entl ftungsfunktion manuellem Neustart und Tastensperre Anschlussspannung 1 230 V 10 15 50 60 Hz Schutzart IP X4D Energiee...

Страница 10: ...ert die F rderh he bei sinkendem Volumenstrom im Rohrnetz auf die H lfte Einsparung von elektrischer Energie durch Anpassung der F rderh he an den Volumenstrombedarf und geringeren Flie geschwindigkei...

Страница 11: ...lsen der Tastgrad gem DIN IEC 60469 1 iPWM 1 Modus Heizungsanwendung Im iPWM 1 Modus wird die Pumpendrehzahl in Abh ngigkeit vom PWM Eingangssignal geregelt Verhalten bei Kabelbruch Wird das Signalkab...

Страница 12: ...eizungssystem wird dabei nicht entl ftet Manueller Neustart Ein manueller Neustart wird durch langes Dr cken 5 Sekunden der Bedientaste aktiviert und deblockiert die Pumpe bei Bedarf z B nach l ngerem...

Страница 13: ...izienz Umw lzpumpe Einbau und Betriebsanleitung Zubeh r Zubeh r muss gesondert bestellt werden detaillierte Auflistung und Beschreibung siehe Katalog Folgendes Zubeh r ist erh ltlich Netzanschlusskabe...

Страница 14: ...Einbau ausschlie lich durch qualifizierten Fachhandwerker WARNUNG Verbrennungsgefahr durch hei e Oberfl chen Pumpengeh use 1 und Nassl ufermotor 2 k nnen hei werden und bei Ber hrung zu Verbrennung f...

Страница 15: ...en abschlie en Rohrsystem sp len Motorkopf drehen Motorkopf 2 5 vor Einbau und Anschlie en der Pumpe drehen Gegebenenfalls W rmed mmschale abnehmen VORSICHT Eine falsche Einbaulage kann die Pumpe besc...

Страница 16: ...ermotor 2 einbauen Dichtungen an den Verschraubungsanschl ssen ein setzen Rohrverschraubungen aufschrauben Pumpe mit einem Maulschl ssel gegen verdrehen sichern und mit den Rohrleitungen dicht verschr...

Страница 17: ...eht unmittelbare Lebensgefahr Vor allen Arbeiten Spannungsversorgung trennen und gegen Wiedereinschalten sichern Niemals das Regelmodul 6 ffnen und niemals Bedienelemente entfernen VORSICHT Getaktete...

Страница 18: ...hlussleitung weder Rohr leitungen noch Pumpe ber hrt Anschluss Netzkabel Netzanschlusskabel montieren Fig 3 1 Standard 3 adriges umspritztes Kabel mit Messing Aderendh lsen 2 Optional Netzkabel mit 3...

Страница 19: ...legung PE N L beachten Vorhandenen Stecker des Ger tes am Steckeran schluss 12 des Regelmoduls anschlie en iPWM Anschluss iPWM Signalkabel Zubeh r anschlie en Stecker des Signalkabels am iPWM Anschlus...

Страница 20: ...ken abwech selnd im Abstand von 1 Sekunde Zum Abbrechen die Bedientaste 3 Sekunden dr cken 7 2 Regelungsart einstellen Regelungsart ausw hlen Die LED Auswahl der Regelungsarten und den dazugeh rigen K...

Страница 21: ...II wieder erreicht LED Anzeige Regelungsart Kennlinie 1 Konstant Drehzahl II 2 Konstant Drehzahl I 3 Differenzdruck variabel p v III 4 Differenzdruck variabel p v II 5 Differenzdruck variabel p v I 6...

Страница 22: ...auf die gleiche Weise wie die Aktivierung 8 Au erbetriebnahme Pumpe stillsetzen Im Falle von Besch digungen an der Anschlussleitung oder anderen elektrischen Komponenten Pumpe umgehend stillsetzen Pu...

Страница 23: ...g Pumpe l uft bei eingeschalteter Stromzufuhr nicht Elektrische Siche rung defekt Sicherungen berpr fen Pumpe hat keine Spannung Spannungsunterbrechung beheben Pumpe macht Ger usche Kavitation durch u...

Страница 24: ...berspannung Zu geringe hohe netzseitige Spannungsversorgung Netzspannung und Einsatzbedingun gen berpr fen Kundendienst anfordern Modul bertempe ratur Modulinnenraum zu warm Kurzschluss Zu hoher Motor...

Страница 25: ...r die Bedientaste aktivieren 5 Sekunden dr cken dann loslassen Die Neustartfunktion wird gestartet Dauer max 10 Minuten Die LEDs blinken nacheinander im Uhrzeigersinn Zum Abbrechen die Bedientaste 5 S...

Страница 26: ...gesehenen zertifi zierten Sammelstellen abgeben rtlich geltende Vorschriften beachten Informationen zur ordnungsgem en Entsorgung bei der rtlichen Gemeinde der n chsten Abfallentsor gungsstelle oder b...

Страница 27: ...dditionally the instructions and safety instruc tions in the other sections must be followed Failure to follow the installation and operating instruc tions will result in the risk of injury to persons...

Страница 28: ...possible total loss NOTICE Useful information on handling the product Symbols These instructions use the following symbols Personnel qualifications Personnel must Be instructed about locally applicabl...

Страница 29: ...mmencing work disconnect the product from the mains and safeguard it from being switched on again The connection must be protected by means of a residual current device RCD The product must be earthed...

Страница 30: ...nection Function High efficiency circulator for hot water heating sys tems with integrated differential pressure control Con trol mode and delivery head differential pressure are adjustable The differ...

Страница 31: ...ed pump curve I II III within the control mode LED indicator combinations during pump venting function manual restart and key lock Connection voltage 1 230 V 10 15 50 60 Hz Protection class IPX4D Ener...

Страница 32: ...delivery head to half in the case of decreasing volume flow in the pipe network Electrical energy saving by adjusting the delivery head to the volume flow requirement and lower flow rates There are t...

Страница 33: ...he duty cycle in accordance with DIN IEC 60469 1 iPWM 1 mode heating application In iPWM 1 mode the pump speed is controlled according to the PWM input signal Behaviour in the event of a cable break I...

Страница 34: ...pump The heating system is not vented Manual restart A manual restart is initiated by pressing and holding the operating button for 5 second and unblocks the pump if required e g after long standstil...

Страница 35: ...nd operating instructions Accessories Accessories must be ordered separately For a detailed list and description consult the catalogue The following accessories are available Mains connection cable iP...

Страница 36: ...tion May only be installed by qualified technicians WARNING Risk of burns from hot surfaces Pump housing 1 and glandless motor 2 may become hot and cause burns if touched During operation only touch t...

Страница 37: ...and brazing work Flush the pipe system Rotating the motor head Rotate the motor head 2 5 before installing and con necting the pump If necessary remove the thermal insulation shell CAUTION An incorre...

Страница 38: ...ally without mechanical tension Place gaskets in the screwed connections Screw on threaded pipe unions Use an open end wrench to secure the pump against twisting and screw tightly to piping Re mount t...

Страница 39: ...voltage Immediate risk of fatal injury if live components are touched Before commencing work switch off the power sup ply and secure it from being switched on again Never open the control module 6 and...

Страница 40: ...mains connection cable Fig 3 1 Standard 3 core coated cable with brass ferrules 2 Optional Mains cable with 3 pin connection plug 3 Optional Wilo Connector cable Fig 3 item b Cable assignment 1 yellow...

Страница 41: ...xisting device plug to the plug connec tion 12 of the control module iPWM connection Connecting the iPWM signal cable accessories Connect the signal cable plug to the iPWM connection 11 until it snaps...

Страница 42: ...s flash in turn at 1 second intervals To cancel press and hold the operating button for 3 seconds 7 2 Setting the control mode Select control mode The LED selection of control modes and corresponding...

Страница 43: ...urve III LED display Control mode Pump curve 1 Constant speed II 2 Constant speed I 3 Variable differential pressure p v III 4 Variable differential pressure p v II 5 Variable differential pressure p...

Страница 44: ...activated in the same manner as it is activated 8 Decommissioning Shutting down the pump Shut down the pump immediately if the connecting cable or other electrical components are damaged Disconnect th...

Страница 45: ...Pump is not running although the power supply is switched on Electrical fuse defective Check fuses No voltage supply at pump Rectify the power interruption Noisy pump Cavitation due to insufficient su...

Страница 46: ...oo low high on mains side Check mains voltage and operating conditions and request customer service Excessive temperature of module Module interior too warm Short circuit Motor current too high Flashe...

Страница 47: ...the operating button press and hold for 5 seconds then release The restart function is initiated and lasts max 10 minutes The LEDs flash in succession clockwise To cancel press and hold the operating...

Страница 48: ...products at designated certi fied collection points Observe the locally applicable regulations Please consult your local municipality the nearest waste disposal site or the dealer who sold the produc...

Страница 49: ...signes essentielles qui doi vent tre respect es lors du montage du fonctionne ment et de l entretien Respecter en outre les instructions et consignes de s curit dans les autres chapitres La non observ...

Страница 50: ...respect peut entra ner des blessures tr s graves ATTENTION Le non respect peut causer des dommages mat riels voire une perte totale du produit AVIS Remarque utile sur le maniement du produit Symboles...

Страница 51: ...lis s par un lectricien qualifi Observer les directives normes et dispositions natio nales en vigueur ainsi que les consignes du fournis seur d nergie relatives au raccordement au r seau lectrique loc...

Страница 52: ...ps de pompe avec raccords filet s 2 Moteur rotor noy 3 Circuits d vacuation des condensats 4x sur la circonf rence 4 Vis du corps 5 Module de r gulation 6 Plaque signal tique 7 Touche de commande pour...

Страница 53: ...le en m avec Q 0 m h 50 50 puissance absorb e max en watt SC SC autor gulation Self control iPWM1 r gulation externe via un signal iPWM1 iPWM2 r gulation externe via un signal iPWM2 12 Position du mod...

Страница 54: ...S lectionner le mode de r gulation S lectionner la courbe caract ristique I II III dans le mode de r gulation Maintenir la touche enfonc e Activer la fonction de purge appuyer pendant 3 secondes Activ...

Страница 55: ...es applica tions sans courbe caract ristique du r seau variable p ex pompes de charge de chauffe eau ainsi que des syst mes de chauffage monotube avec radiateurs La r gulation maintient la hauteur man...

Страница 56: ...ne rupture de c ble la pompe acc l re la vitesse de rota tion maximale Entr e de signal PWM 5 La pompe fonctionne la vitesse de rotation maximale 5 85 La vitesse de rotation de la pompe baisse de mani...

Страница 57: ...manuel Le red marrage manuel s effectue en appuyant lon guement 5 secondes sur la touche de commande et d bloque la pompe si n cessaire p ex apr s un arr t prolong en t Verrouiller d verrouiller les t...

Страница 58: ...d r e comme non conforme et entra ne la perte de tout droit la garantie AVIS Ajouter uniquement des m langes pr ts l emploi dans l installation Ne pas utiliser la pompe pour m langer le fluide dans l...

Страница 59: ...er aussit t apr s la livraison l absence de d t riorations dues au transport et l int gralit de la livraison et le cas ch ant r clamer imm diatement Conditions de transport et de stockage Assurer une...

Страница 60: ...er des br lures Respecter les points suivants avant de monter ou de d monter la pompe ou de desserrer les vis du corps 4 Laisser refroidir compl tement le syst me de chauf fage Fermer les vannes d arr...

Страница 61: ...d isolation ther mique Maintenir la t te du moteur 2 5 et d visser les 4 vis du corps 4 Faire tourner la t te du moteur 2 5 pr cautionneusement Respecter la position de montage autoris e Fig 2 et la...

Страница 62: ...cords filet s Visser les raccords filet s Bloquer la pompe l aide d une cl fourche contre toute torsion et visser la tuyauterie de mani re tanche Le cas ch ant r installer la coquille d isolation ther...

Страница 63: ...per l ali mentation lectrique et la prot ger contre toute remise en service Ne jamais ouvrir le module de r gulation 6 et ne jamais retirer des l ments de commande ATTENTION Une tension d alimentation...

Страница 64: ...r un c ble de raccordement r sistant la cha leur si la temp rature du fluide d passe 90 C S assurer que le c ble de raccordement ne touche ni les tuyauteries ni la pompe Raccordement du c ble d alimen...

Страница 65: ...le c ble de raccordement de l alimenta tion lectrique Appuyer sur le bouton de verrouillage de la fiche mont e et retirer la fiche du module de r gulation Respecter l affectation des bornes PE N L Rac...

Страница 66: ...s rel cher La fonction de purge d marre et dure 10 minutes Les rang es de LED sup rieures et inf rieures cligno tent en alternance intervalle d une seconde Pour annuler appuyer pendant 3 secondes sur...

Страница 67: ...ande Les LED indiquent le mode de r gulation et la courbe caract ristique param tr s Repr sentation des r glages possibles dans l ordre indiqu ci contre partir du r glage d usine vitesse de rotation c...

Страница 68: ...rel cher Les LED clignotent en permanence intervalle d une seconde Le verrouillage des touches est activ les r glages de la pompe ne peuvent plus tre modifi s La d sactivation du verrouillage des touc...

Страница 69: ...sur les c bles de raccordement ou d autres composants lectriques Couper la pompe de l alimentation lectrique Contacter le service apr s vente Wilo ou un artisan sp cialis 9 Entretien Nettoyage Nettoy...

Страница 70: ...le lectrique d fectueux V rifier les fusibles Absence de tension sur la pompe Rem dier la coupure de la tension La pompe met des bruits Cavitation provoqu e par une pression d entr e insuffisante Augm...

Страница 71: ...e Contr ler la tension d alimentation et les conditions d utilisation contacter le service apr s vente Temp rature excessive du module Int rieur du module trop chaud Court circuit Intensit moteur tro...

Страница 72: ...is rel cher La fonction de red marrage se lance et dure 10 minutes max Les LED clignotent les unes apr s les autres dans le sens des aiguilles d une montre Pour annuler appuyer pendant 5 secondes sur...

Страница 73: ...x centres de collecte certifi s pr vus cet effet Respecter les prescriptions locales en vigueur Pour des informations sur l limination correcte s adres ser la municipalit locale au centre de traitemen...

Страница 74: ...2 0 3 1 1 9 0 0 1 0 3 0 0 1 0 0 1 7 0 03 7 1 0 1 7 01 1 1 1 7 1 1 7 0 685 12 2 86 9 2 0 1 6 5 1 9640 1 9 8 697 9 9 3 19 9 3 91 4 1 2 1 17 3 6 6 6 86 29 6 64 9 9 2 4 1 9 8 9 7 1 4 1 9 A 9A 9A 1 10 3 1...

Страница 75: ......

Страница 76: ......

Страница 77: ...HJUDWH 0 7 ZLOR LWDOLD ZLOR LW D DNKVWDQ 2 HQWUDO VLD OPDW 7 LQIR ZLOR N RUHD 2 3XPSV WG DQJVHR XVDQ 7 ZLOR ZLOR FR NU DWYLD 2 DOWLF 6 5LJD 7 LQIR ZLOR OY HEDQRQ 2 121 6 5 GHLGHK HEDQRQ 7 LQIR ZLOR FR...

Отзывы: