Installation

• Only install the pump after all welding and soldering work has 

been completed and, if necessary, the pipe system has been 
flushed through.

• Mount the pump in a readily accessible place for easy inspection 

and dismantling.

• When installing in the supply leg of open systems, the safety 

supply must branch off upstream of the pump (DIN EN 12828).

• Install check valves upstream and downstream of the pump to 

facilitate a possible pump replacement. 
• Perform installation so that any leaking water cannot drip 

onto the control module. 

• To do this, align the upper gate valve laterally.

• In thermal insulation work, make sure that the pump motor and 

the module are not insulated. The condensate drain openings 
must remain uncovered.

• Install without tension and with the pump motor in the hori-

zontal position. See fig. 3 for installation positions of the pump.

• Direction arrows on the pump housing indicate the direction of 

flow.

• If the installation position of the module is changed, the motor 

housing has to be turned as follows:
• Loosen the internal hexagon screws,
• Turn the motor housing, including control module.

CAUTION! Risk of damage to the pump!
The gasket may be damaged when the motor housing is 
turned. Replace defective gaskets immediately.

• Twist the internal hexagon screws back in and tighten them,

Содержание Wilo-E 15/1-5

Страница 1: ...llation and operating instructions D Einbau und Betriebsanleitung F Notice de montage et de mise en service I Istruzioni di montaggio uso e manutenzione RUS Wilo E 15 20 25 30 1 5 4 523 144 Ed 01 2011...

Страница 2: ...Fig 1 Fig 2a Fig 2b H Q H max H H min H Q H max H H min...

Страница 3: ...Fig 3 Fig 4 1 a b 2 3...

Страница 4: ...GB Installation and operating instructions 3 D Einbau und Betriebsanleitung 13 F Notice de montage et de mise en service 23 I Istruzioni di montaggio uso e manutenzione 34 RUS 45...

Страница 5: ......

Страница 6: ...he product and the underlying safety standards valid at the time of going to print EC declaration of conformity A copy of the EC declaration of conformity is a component of these operating instruction...

Страница 7: ...f inju ries WARNING The user can suffer serious injuries Warning implies that serious injury to persons is probable if this information is disregarded CAUTION There is a risk of damage to the product...

Страница 8: ...s Property damage 2 4 Safety instructions for the operator The existing directives for accident prevention must be adhered to Danger from electrical current must be eliminated Local direc tives or gen...

Страница 9: ...fications to the pump system are only permitted after consultation with the manufacturer Original spare parts and accessories authorised by the manufacturer ensure safety The use of other parts can nu...

Страница 10: ...th con stantly changing volume flows Approved fluids are heating water in accordance with VDI 2035 water glycol mixture at a mixing ratio of max 30 of glycol If glycol is added the deliv ery data of t...

Страница 11: ...tion must be carried out in accordance with local regulations and only by qualified per sonnel WARNING Risk of personal injury The existing directives for accident prevention must be adhered to DANGER...

Страница 12: ...do this align the upper gate valve laterally In thermal insulation work make sure that the pump motor and the module are not insulated The condensate drain openings must remain uncovered Install witho...

Страница 13: ...Hz 2 N neutral conductor 3 Earth conductor The mating plug to the OEM plug can be ordered with one of the following suppliers Wilo does not assume any liability for the products supplied by these manu...

Страница 14: ...a 2b and delivery head Turn the red button fig 4 a to select the control mode symbol and adjust the desired delivery height between 1 m and 5 m Variable differential pressure p v fig 2a The differenti...

Страница 15: ...e should always be recti fied by a qualified electrician only 10 Faults causes and remedies Faults Causes Remedy Pump is not running although the cur rent entry is switched on Electrical fuse defectiv...

Отзывы: