English
46
WILO SE 10/2013
Engine does not start or try to start, then
stop
Unloaded batteries
Check battery and loader of battery.
Load battery and replace them if neces-
sary
Lack of fuel
If it is not indicated on the control panel
indicating light, check the fuel tank and
alarm float. Replace.
Replace the tank.
Air in fuel circuit
Remove air from circuit by draining the
injectors and diesel fuel strainers.
Dirty fuel strainer
Replace.
Dirty air strainer
Replace.
Fuel circuit failure : injectors blocked,
injection pump failure
Call customer service centre.
Too low temperature
Check that ambient temperature is not
less than 10
°
C. Then check the correct
working of oil/water heater.
Replace.
Loosened or rusty connections between
battery/starter/relay
Check cables and terminals.
Re-wire. Correctly tighten
Replace.
Diesel pump control panel failure
Check and replace if necessary
Starter failure
Call customer service centre.
Black smoke
Dirty/blocked air strainer
Replace.
Too high oil level
Remove oil excess.
Problem with injector, fuel pump, etc.
Call customer service centre.
Unusual heating – too high water/oil
temperature
Pump overload (frictions)
Dismantle and check.
Coupling out of axis
Align correctly.
Ambient temperature higher than 40°C
Ventilate the space.
Insufficient ventilation
Check filters and
ventilation grille. Clean
or resize.
Dirty or blocked radiator/coolant
Dismantle and clean.
Lack of water in radiator/heat exchanger After the cooling, fill with water and
check for if leaks are present.
Closed or not open enough heat
exchanger circuit valve
Check that pump has a water flow, then
open the butterfly valve.
Water circulation pump failure
Call customer service centre.
Fan belt failure (air-cooled engines)
Check voltage and replace if necessary.
Corresponding alarm failure
Check sensor, connections and control
unit on control panel. Replace if neces-
sary.
Jockey pump does not start
No power supply
Check connections and the electric
panel.
The pressure switch is calibrated to a
lower pressure than the main pump.
Check the pressure switch settings.
Short-circuit in winding
Check winding.
Intervention of the thermal protection
Check the sizing of the supply line.
Check that the pump is not locked, then
check pressure switch setting and the
tank inflation.
Control box failure and wrong connec-
tions
Check.
Faults
Causes
Remedy
Содержание SiFire
Страница 2: ...Fig 1 Fig 2a A 2 2 E B C D...
Страница 3: ...Fig 2b Fig 3 21 25 26 13 11 12 19 15 22 27 20 24 23 2 1 14 4 16 7 5 6 10 18 17 9 9 10 8 3...
Страница 4: ...Fig 4 Fig 5...
Страница 5: ...Fig 6a 3 5 D D 4 D 2 3 C min max 1 8 m s Fig 6b min 3 5 D D 4 D max 2 m 2 3 C max 1 8 m s...
Страница 6: ...Fig 7 Fig 8 max 3 2 m min A B C D 2 4 5 6 3 8 7 1...
Страница 7: ...Fig 9a Fig 9b A B C D 800 800 800...
Страница 8: ...Fig 1a Fig 9a variant Fig 9b variant A B C D 800 800 800...
Страница 9: ...Fig 10 Fig 11 1 2 1 2 1...
Страница 10: ......
Страница 34: ......
Страница 35: ......