15
with the carrier within the allowed time. Prior
to installation of the pump, please check that all
bolts are tightened that may have loosened during
the transportation process (particularly between
motor and motor bracket). Please handle the pump
carefully so as not to damage the unit. Refer to
Fig. 3 (page 3) - Proper Lifting
for proper lifting
procedures and guidelines.
CAUTION
! Outside influences may cause damages !
If the delivered material is to be installed later on,
store it in a dry place and protect it from impacts.
4. Application
4.1 Allowable pump liquids
This pump’s basic function is to pump hot or cold
water, water with glycol or other low viscosity
fluids that contain no mineral oil, solid or abrasive
substances or materials having long fibres. The
manufacturer’s approval is required for use to
pump corrosive chemicals. Please refer to
(pages 4-5) -Allowable liquids to be pumped
.
DANGER! Risk of explosion!
Do not use this pump to handle flammable or
explosive liquids.
4.2 Application areas:
Water Supply and Pressure Boosting:
• Pressure boosting in buildings, hotels,
residential complexes
• Pressure booster stations supply of water
networks
• Pressure boosting for industrial water supply
Irrigation and Agriculture:
• Greenhouse
• Sprinkler irrigation
•
Field irrigation (flooding)
Light Industry:
• Washing and cleaning systems
• Car washing facilities
•
Fire fighting systems
• Process water systems
• Machine tools (cooling lubricants)
Water Treatment:
• Water softeners and de-mineralization
• Reverse Osmosis systems
• Filtration
•
Ultra-filtration systems
• Distillation systems
Heating, Ventilation and Air-Conditioning:
• Boilers
• Induction heating
• Heat exchangers
• Refrigerators
• Cooling towers and systems
• Temperature control systems
5. Technical data
5.1 Technical data
- Maximum operating pressure please
(page 6) - Maximum Operating Pressure and Inlet
• Maximum suction pressure: 145 PSI (10 BAR)
- Temperature range
• Fluid temperature:
5 to 248°F (120°C)
• Ambient temperature:
32 to 104°F (40°C)
WARNING
If ambient temperatures are above 104°F, or if the pump is
located at elevations more than 3,281 feet (1,000 meters)
above sea level, the motor’s output must be decreased to
compensate for less effective cooling, and may have to be
replaced with a stronger motor.
5.2 Scope of Supply
• Multistage pump.
• Installation and operating instructions.
5.3 Accessories
Original accessories are available for the MVI range.
The accessories must be ordered separately.
6. Description and function
6.1 Product description
Fig. 6a (page 7) - MVI - 5, 15, 20, 50, 75, 100
12 – chamber
18 – impeller
24 – neck ring
36 – pedestal
37 – shaft
44 – coupling
48 – outer sleeve
56 – cover, seal chamber
57 – mechanical seal
59 – pump volute
62 – baseplate
82 – O-ring
Fig. 6b (page 7) - MVI - 160, 225, 320, 450 Section
12 – chamber
14 – bearing ring
18 – impeller
24 – neck ring
36 – cover, seal chamber
37 – shaft
42 – bottom bearing ring
48 – outer sleeve
53 – pedestal
57 – mechanical seal
59 – pump volute
62 – baseplate
82 – O-ring
Fig. 6c (page 8) - MVI - 600, 750 Section View
12 – chamber
17 – bearing ring
Installation and operating instructions - MVI 5, 15, 20, 50, 75, 100, 160, 225, 320, 450, 600, 750
Содержание MVI 15
Страница 8: ...MVI 600 750 Fig 6c MVI 600 750 Section View Fig 7a Proper Installation Clearances 10 8...
Страница 12: ...Figure 7j Proper pump mounting 5 1 2 3 3 4 2 1 6 7 Fig 7k Proper piping 12...
Страница 21: ...21 Installation and operating instructions MVI 5 15 20 50 75 100 160 225 320 450 600 750...