27
Installation and operating instructions – Wilo-Helix VE / MVIE 11/15/18,5/22kW – IE5
English
8.3.2 Display structure
Pos.
Description
1
Menu number
2
Value display
3
Unit display
4
Standard symbols
5
Icon display
8.3.3 Description of standard symbols
Symbol
Description
Operation in “Speed stage control”
mode
Operation in “Constant pressure”
or “PID control” mode
Operation in “Variable pressure”
or “PID control” mode
2
IN2 input activated
(external setpoint)
Access lock
When this symbol appears, the set-
tings or current measurement values
cannot be modified. The information
is displayed in read-only form
BMS (Building Management System)
PLR or LON is activated
Pump in operation (if flashing, zero
delivery rate detection detected)
Pump switched off
8.3.4 Display
Display status page
• The status page appears as the default page of
the display.
The currently set setpoint is displayed. Basic
settings are displayed by symbols.
Example of display status page
NOTICE: In all menus, if the rotary knob is not
operated within 30
seconds, the display will reap-
pear and no change will be registered
.
Navigation element
• The menu structure makes it possible to call
up the functions of the converter. A number is
attributed to every menu and submenu.
• Turn the rotary knob to scroll through any menu
level (e.g. 4000 -> 5000).
• Blinking elements (value, menu number, symbol
or icon) allow the selection of a new value, a new
menu number or a new function.
Symbol
Description
When the arrow appears:
• An impulse on the rotary knob
provides access to a sub-menu
(e.g. 4000 -> 4100).
When the “return” arrow appears:
• An impulse on the rotary knob
provides access to the higher
menu (e.g. 4130 -> 4100).
8.3.5
Defining the application of an open or closed
hydraulic loop
The product has two types of application. The
type of application chosen defines the operating
modes that can be accessed.
Hydraulic
application
Operating mode
Open loop
“p-c” mode
Speed stage
control mode
PID mode
Closed loop
“Δp-c” mode
“Δp-v” mode
Menu 5.7.8.0 of the EXPERT menu can be used to
select the type of application required.
NOTICE:
The product must be reinitialised when
the application is changed. All the user parame-
ters will revert to the factory settings.
8.3.6
Defining operating modes
Defining pressure sensors
• The relative pressure sensor measures the pres-
sure in relation to atmospheric pressure.
• The absolute pressure sensor measures the pres-
sure in relation to the zero pressure in a vacuum.
• The differential pressure sensor measures the
pressure between two points.
NOTICE:
All the pressures indicated by the pump
are measured in relation to the atmospheric pres-
sure, except when a differential pressure sensor
is used.
Содержание Helix VE 11kW-IE5
Страница 2: ...Fig 1 ...
Страница 3: ...Fig 2 HELIX VE 10 16 ...
Страница 4: ...Fig 2 HELIX VE 22 36 52 ...
Страница 8: ...Fig 9 HELIX VE 22 36 52 Fig 8 x2 x4 ...
Страница 9: ...Fig A1 1 1 ...
Страница 10: ...2 2 4 4 3 3 Fig 2D Fig 3D 4 4 3 3 2 2 Fig 4D 3 3 4 4 2 2 ...
Страница 11: ...en Installation and operating instructions 12 ...
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......