ENGLISH

- Start again the pump.

- If  necessary  (particularly  if  the  suction  height  exceeds  5  m)  repeat 

these operations.

- If water leaks at draining plug (it means the pump delivers its pressure),

slowly open the discharge valve.

- The pump has to be primed. 

- Check pressure stability at discharge with a manometer, if instability, 

perfect air draining.

- In case of failure, do the filling in again and start the operation again.

- To perfect air draining, close the discharge valve and the draining plug, 

then stop the pump 20s, start the pump again and open the draining 
plug. Do it as long as air comes out.

- Open the discharge valve in order to have the wished working point.

- Check that the current input does not exceed the value indicated on 

the identification pump plate.

7. Maintenance

Before any operation,
switch off the pump(s).

No special maintenance in operation.

Keep the pump and the motor-converter perfectly clean.

In case of prolonged stopping, if there is no risk of frost, it is best not
to drain the pump.

The bearing holding the coupling and the motor bearings are lubricated
for their total lifetime and do not require any lubrication.

On  pumps  equipped  with  greaser  under  bearing  box,  see  regreasing
instructions written on sticker put on it.

On other models, the bearing holding the coupling is lubricated for its
total lifetime.

It  is  recommended  to  grease  the  shaft  end  as  well  as  the  coupling
boring with a high adhering grease (type type D321R Molikote or 8191
Loctite for example) to facilitate any further diassembling.

The mechanical seal does not require any maintenance in operation. It
must never operate dry.

19

CAUTION !

-The ”failure transfer” relay is active when the counter reaches 6 failures.

1) If the pump is completely stopped and an intervention on this one is
necessary,  cut  the  supply  ;  correct  the  failure,  switch  on  the  supply
again. 

2) If the failure cause has been suppressed without cutting the conver-
ter supply ; the pump must start again after an impulse on the ”reset”
button (See FIG. 4).

- If the defect is major, the action of an after-sales technician is required.

INCIDENTS

8.1 THE PUMP IS 

OVERLOADED

8.2 ELECTRICAL 

INCIDENTS

8.3 THE MOTOR / 

CONVERTER HEATS

CAUSES

a) The Ventilation of the converter

is uncertain :

b) The pump is obstructed

by foreign matters :

c) The pump is locked :

d) The fluid density is too important :

a) The supply of the converter is in

over-or under-voltage :

b) A supply phase is missing : 

c) The converter or the motor is

in short-circuit :

a) The ventilation of the converter is uncertain :

b) The motor cooling is uncertain :

c) The pump is used in the ambient

temperature higher 40 °C :

REMEDIES

a) Check that the cooling channel is not obstructed.

b) Dismantle the pump, replace the defective

components or clean.

c) Dismantle the pump, clean it and replace the

defective parts.
Possibly mechanical defect of the motor (bearings). 
Clean all the pipework.

d) Limit the maximum loading point of the pump 

according to the type of fluid.

a) Check the voltage at the converter terminals.

b) Check the supply.

c) Dismantle the motor-converter of the pump and 

check it or replace it.

a) Check that the cooling channel is not obstructed 

and that fans run correctly.

b) Clean the cooling ribs of the motor.

c) The motor / converter is foreseen to run at a 

maximum ambient temperature of + 40 °C.

8. Defaults-Causes-Remedies

Before  carrying  out  any  maintenance  work,  switch  off  the
pump  and  ensure  that  it  cannot  be  switched  on  again  by
unauthorised people.

Never carry out work on a running pump.

DEFECTS DETECTED BY THE SPEED VARIATOR

All incidents hereafter mentioned give rise to :
- The resting of the ”available transfer” relay.
- The activation of the ”failure transfer” relay when the maximum quan-

tity of defect is reached.

- ligthening of a red LED.

CAUTION !

GR

EA

SE

MVIE 7004

MVIE 9503/2

Содержание HELIX-VE 11-22 kW

Страница 1: ...g instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften E Instrucciones de instalaci n y funcionamiento I Istruzioni di montaggio uso e manutenzione P Manual de i...

Страница 2: ......

Страница 3: ...25 16 25 16 1606 252 190 215 130 260 260 220 220 30 14 E D mm mm 20 12 2207 2209 25 16 2205 270 190 215 130 5 12 7002 7004 7002 7004 25 16 350 261 280 199 45 14 9501 9503 9501 9503 25 16 350 261 280...

Страница 4: ...2 1 50 mm Min 14 Fig 5 Fig 6...

Страница 5: ...Fig 7...

Страница 6: ...d Beseitigung 12 GB 1 General 14 2 Safety 15 3 Transport and interim storage 15 4 Description and function 15 5 Assembly 16 6 Starting Up 18 7 Maintenance 19 8 Defaults Causes Remedies 19 F 1 G n rali...

Страница 7: ...bient humidity 90 Protection index IP 54 Insulation class F Pump acoustic level tolerance 3dB A 11 kW 78 15 kW 78 18 5 kW 81 22 kW 81 When ordering spare parts please give all the information on the p...

Страница 8: ...energy electric shock or electrocution are to be excluded Safety precautions issued by the local electricity supply company are to be observed 2 5 Safety precautions for the installation The operator...

Страница 9: ...ges counterflanges available as accessories The diameter of the pipe must never be smaller than the one of the counter flange The direction of the fluid flow is indicated on the identification label o...

Страница 10: ...3 Example 6 defects with a variable time limit on 10 sliding feature of the contact min12V 10mA minutes according to the following scale The relay is actived when the pump runs or max250V 1A is in a p...

Страница 11: ...Put a funnel into the venting plug port and completely fill the pump and the suction pipe After water flows out and total air exit filling is achieved Screw the venting plug and the bottom drain primi...

Страница 12: ...the supply correct the failure switch on the supply again 2 If the failure cause has been suppressed without cutting the conver ter supply the pump must start again after an impulse on the reset butt...

Страница 13: ...t tight e Too high losses of load on suction or suction head is too high Check the NPSH of the pump installed and of the installation a Check and tighten completely the nuts of the stud bolts b Have t...

Страница 14: ...spositions suivants dont il rel ve EG Maschinenrichtlinie 98 37 EG EC Machinery directive Directives CEE relatives aux machines Elektromagnetische Vertr glichkeit Richtlinie 2004 1008 EG Electromagnet...

Страница 15: ......

Страница 16: ...G EMV Elektromagnetisk kompatibilitet 2004 1008 EG EG Lavspenningsdirektiv 2006 95 EG Anvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vastaa...

Страница 17: ...lint Budapest T 36 23 889500 wilo wilo hu Ireland WILO Engineering Ltd Limerick T 353 61 227566 sales wilo ie Italy WILO Italia s r l 20068 Peschiera Borromeo Milano T 39 25538351 wilo italia wilo it...

Страница 18: ...63 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 Erreichbar Mo Fr von 7 17 Uhr Wochenende und feiertags 9 14 Uhr elektronische Bereitschaft mit R ckruf Garantie Kundendien...

Отзывы: