 ENGLISH 

 

 

15 (55) 

The green diode

 

(pos. 10) indicates normal pump operation. 

The switch unit contains the electronic as well as the terminal block for power 
supply and pump motor. The signal/operating elements at the switchbox cover 
are (Fig. 2) 

 

Yellow LED:  Mains power is on, the pump is on ready standby, (pos. 9) 

 

Green LED:  Pump runs, (pos. 10) 

 

Red 

LED: Any fault leading to pressure loss in the 

 

 

pipe system, (pos. 11) 

 

Reset button: After fault rectification the reset button (pos. 8) must be kept 
pushed until the system is fully pressurized. This is also valid for renewed 
start-up, otherwise the pump will again fail due to insufficient system 
pressure. 

4.2  Scope of Supply 

 

Wilo-Fluidcontrol (EK- integrated 1.5 m connecting 
cable). 

 

Installation and Operating Instructions. 

 

5 Siting/Installation 

5.1 Installation 

For installation and mounting requirements refer to the pump installation and 
operating instructions. 
The arrow at the housing indicates direction of flow. 
The WILO-Fluidcontrol must only be mounted into a vertically run discharge 
pipe. 

 

The WILO-Fluidcontrol to be screwed onto the discharge port of the pump 
using 
suitable connecting fittings, to be sealed with hemp or Teflon band. 

 

If the water column between pump and highest outlet tap exceeds 15 m, 
the unit must be installed at a higher level in the discharge pipe ensuring 
a maximum vertical head onto the unit of not more than 15 m. In such 
case no outlet tap must be located at a level below that of the WILO-
Fluidcontrol (Fig. 3). 

 

In order to avoid noise transmission from the pump onto the pipe system 
it is recommended to provide and install a flexible connector at the 
discharge side of theWILO-Fluidcontrol. 

Содержание fluidcontrol ek

Страница 1: ...eitung GB Assembly Instructions F Notice de montage NL Inbouw en gebruikshandleiding E Instrucciones de instalaci n y funcionamiento I Istruzioni di montaggio uso e manutenzione 2 049 542 ed04 0804 H...

Страница 2: ...1 4 3 2 5 6 12 Fig 1 10 11 9 8...

Страница 3: ...Fig 2 Fig 2...

Страница 4: ...220 240 V 50 60 Hz M 1 L1 N U V Fig 4 7 Fig 5...

Страница 5: ...erating instructions 12 Notice de montage et de mise en service 18 Inbouw en gebruikshandleiding 24 Instrucciones de instalaci n y funcionamiento 30 Istruzioni di montaggio uso e manutenzione 36 Be p...

Страница 6: ...supply Single phase 1 220 250V 50 60 Hz F L C max 10 A Enclosure IP 65 Connections suction discharge 1 BSP The shut off head generated by the applicable pump must be approx 0 5 bar higher than the 2...

Страница 7: ...hazards to persons due to electrical and or mechanical causes 2 4 Safety notes for the Operator Local regulations regarding the prevention of accidents must be observed Hazards from electrical energy...

Страница 8: ...or stop and connection box for pump and network 5 Hydraulic chamber with diaphragm 6 Compensating chamber with spring 7 Adjusting screw for starting pressure of the pump 8 Reset button St rungs quitti...

Страница 9: ...and Operating Instructions 5 Siting Installation 5 1 Installation For installation and mounting requirements refer to the pump installation and operating instructions The arrow at the housing indicat...

Страница 10: ...imum however 10 A inert Strictly adhere to local earthing regulations If required see VDE 0100 a ground fault circuit interruptor GFCI switch must be provided and installed by others 6 Commissioning F...

Страница 11: ...t button Pump does not generate sufficient pressure Leakage loss greater than 0 6 l min Pump runs irregularly defekt printed circuit board Pump does not generate sufficient pressure air Leakage loss g...

Страница 12: ...Budapest T 36 23 889500 wilo wilo hu Ireland WILO Engineering Ltd Limerick T 353 61 227566 sales wilo ie Italy WILO Italia s r l 20068 Peschiera Borromeo Milano T 39 25538351 wilo italia wilo it Kazak...

Страница 13: ...63 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 Erreichbar Mo Fr von 7 17 Uhr Wochenende und feier tags 9 14 Uhr elektroni sche Bereitschaft mit R ckruf Garantie Kundendi...

Отзывы: