background image

the current marked on the motor data plate.

– The single-phase motor has built-in thermal protection.

– Provide a fuse disconnecting switch (type aM) to protect the power 

supply.

Line power

– Use a cable meeting standard board.
• 

THREE-PHASE

  : 4 conductors (3 EARTH)

• 

TWO-PHASE

  

: 3 conductors (2 EARTH).

A  connection  error  would  damage  the  motor.  The  power 

cable  must  never  touch  the  pipe  or  the  pump;  make  sure 

that it is away from any moisture.

The electric connections should be made as shown by the diagrams 

inside the cover of the motor terminal box (or see figure 3).
– The  electric  motors  used  with  pumps  can  be  connected  to  a  fre-

quency converter.

  Strictly follow the directions given by the manufacturer’s data sheet.

– The converter must not generate voltage peaks at the motor termi-

nals higher than 850 V and dU/dt (Voltage/Time variation) higher than 

2500  V/µs.  If  the  value  of  the  voltage  signal  are  higher  than  those, 

risk of damage the motor are to forecast.

  If  it  does,  place  an  LC  (inductance-capacitance)  filter  between  the 

converter and the motor.

  It  must  be  connected  to  the  motor  with  a  minimum  length  cable, 

armoured if necessary.

DO NOT FORGET TO CONNECT THE EARTH.

6. Starting up

6.1  Prior cleaning

An hydraulic test is canted out on each pump in our factory. 

Some water stays inside them. It is recommended for hygien 

reasons to clean the pump before using it on the potable 

water supply.

6.2  Filling, degassing

WARNING!

Never operate the pump dry, even briefly.

Pump under pressure

 (figure 2)

– Close the discharge valve (item 3).

– Open the suction valve (item 2).

– Unscrew the filling plug (item 5) on the main body of the pump.

– Put a funnel into the port and slowly and completely fill the pump and 

the suction pipe.

– When water flows out and all air has been eliminated, filling is com-

plete.

– Screw the plug back in.

Pump in suction :

 two cases are possible :

1st CASE 

(figure 4-1) : 

– Close the discharge valve (item 3).

– Open the suction valve (item 2).

– Unscrew the filling plug (item 5) on the main body of the pump.

– Put a funnel into the port and slowly and completely fill the pump and the 

suction pipe.

– When water flows out and all air has been eliminated, filling is complete.

– Screw the plug back in.

2nd CASE 

(figure 4-2) : 

Filling can be made easier by fitting, on the pump suction pipe, a verti-

cal pipe with a stopcock and a funnel.

- Close the discharge valve (item 3).

- Open the suction valve (item 2).

- Unscrew plug (item 5).

- Fill the pump and the suction pipe completely, until water flows out 

of the bleed device and all air bubbles have disappeared.

– Close  the  stopcock  (which  can  be  left  in  place),  remove  the  pipe, 

and screw the filling plug back in.

– Start  the  motor  by  pressing  briefly,  wait  for  20’  to  let  air  going  up 

inside pump housing.

– Unscrew  once  again  the  plug  (item  5)  and,  if  a  water  flow  doesn’t 

appear, remove plug and complete the water level inside the pump. 

Close the plug and start again.

– If necessary, repeat this operation.

NOTE

: We recommend to protect the pump against dry-running with 

an adequate device (automatic control, float switch, pressure switch).

6.3  Check dislocking and the motor sense of rotation

Whith an open-end screwdriver placed in the slot of the shaft on fan 

side, make sure that the pump turns freely without sticking.

Switch on the motor by short pressing on the motor-overload release 

and check that it turns in the direction indicated by the arrow located 

on the indentification label of the pump.

If not, interchange two phase wires on the motor terminal block or cir-

cuit-breaker.

NOTE

:  The  single-phase  motors  are  designed  to  turn  in  the  right 

direction in all cases.

6.4 Starting up

Depending on conveyed fluid and running of pump, surface 

temperature can exceed 68°C. Take necessary means to 

avoid injuries.

WARNING!

The pump must not be operated in a no-flow condi-

tion (discharge valve closed) for more than 10 minu-

tes.

We  recommend  establishing  a  minimum  flow  of  about  10  %  of  the 

rated capacity of the pump, to avoid the formation of a gas pocket at 

the top of the pump.
– Open the discharge valve to start the pump.

– Use a pressure gauge to check the stability of the discharge pressu-

re; if it is unstable, bleed the pump again or perform the filling opera-

tion.

– Check that the current draw does not exceed the value marked on 

the motor data plate.

7. Servicing

Before any operation, switch off the pump(s).

No  special  servicing  in  operation.  Always  keep  the  pump  perfectly 

clean.

For a prolonged shutdown, if there is no risk of frost, it is best not to 

drain the pump.

To avoid any blocking of the shaft and the hydraulic system, in frosty 

periods, empty the pump by removing the plug (item 6) and the filling 

plug (item 5). Screw the 2 plugs back in, without tightening them.

The  replacement  frequencies  for  the  mechanical  seal  will  depend  on 

pump operating conditions, namely:

• For the mechanical seal, the temperature and pressure of the liquid 

pumped

• For  the  motor  and  other  components,  pressure  head  and  ambient 

temperature.

• Priming frequency, duty continuous or periodic.

The mechanical seal do not require special servicing in operation.

Bearings are lubricated for lifetime and do not require any lubrication.

12

WILO SE 04/2016

English

Содержание Economy MHIL

Страница 1: ...8 957 Ed 05 2016 08 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento it Istru...

Страница 2: ...Fig 1 Fig 2...

Страница 3: ...Y HIGH VOLTAGE LOW 3 1 1 Fig 3 Fig 4...

Страница 4: ......

Страница 5: ...1 single phase motor 3 three phase motor Mains voltage V Frequency Hz 2 poles Manufacturer s key IE3 motor Permissible temperature range 15 C to 90 C Maximum ambient temperature 40 C Maximum permissib...

Страница 6: ...f the opera ting instructions The limits given in the catalogue or data sheet must under no circumstances be exceeded 3 Transport and Storage WARNING During transport and in storage the pump must be p...

Страница 7: ...the bleed device and all air bubbles have disappeared Close the stopcock which can be left in place remove the pipe and screw the filling plug back in Start the motor by pressing briefly wait for 20...

Страница 8: ...on suction or suc tion head is too high check the NPSH of the installed pump Cross the two phase wires on motor ter minal block or motor overload release to reverse the sense of rotation Check the vol...

Страница 9: ...also with the following relevant harmonized European standards sont galement conformes aux dispositions des normes europ ennes harmonis es suivantes EN 60034 1 EN 60204 1 N 2117790 02 CE A S n 4096242...

Страница 10: ...9 125 EK 2006 42 2014 30 2009 125 EO WILO SE prohla uje e v robky uveden v tomto prohl en odpov daj ustanoven m n e uveden ch evropsk ch sm rnic a n rodn m pr vn m p edpis m kter je p ej maj Stroje 20...

Страница 11: ...prodotti spe ifikati f din id dikjarazzjoni huma konformi mad direttivi Ewropej li jsegwu u mal le islazzjonijiet nazzjonali li japplikawhom WILO SE verklaart dat de in deze verklaring vermelde produc...

Страница 12: ......

Страница 13: ......

Страница 14: ...2785961 info wilo kz Korea WILO Pumps Ltd 618 220 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 5229 info wilo lv Lebanon WILO LEBANON SARL Jdeideh 1202 2...

Страница 15: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: