English
30
WILO SE 06/2010
8.2 Modbus IF-Module
Set data format with parameter C in the pump menu 5.2.5.0 in accordance with
the following table:
8.3 BACnet IF-Module
The BACnet instance number is set with the parameters
C (in the pump menu 5.2.5.0)
E (in the pump menu 5.2.6.0)
F (in the pump menu 5.2.7.0)
This requires conversion into a hexadecimal value
1
) (indicated in the following
by an ‘h’ suffix)
.
The instance number is divided between the three parameters (example 4660):
• Convert the instance number into a hexadecimal value (1234h)
Parameter C
Parity*
Data bits
Stop bits
3
N
8
2
6
S
8
1
10
O
8
1
* N – no parity, E- even parity, O – odd parity
All other settings are reserved for expansions (see also the protocol description).
1)
For example with the calc.exe program in the scientific view