  Troubleshooting

Troubleshooting — Common problems and possible solutions

Symptom

Common Causes

Possible Corrections

Rapid cycling — boiler 
turns on and off 
frequently

Thermostat installed where drafts or 
heat affect reading

Locate thermostat on inner wall away from heat sources or cool drafts.

Heat anticipator in thermostat 
adjusted incorrectly

Adjust thermostat per manufacturer's instructions.

Incorrect limit setting

Set limit according to system needs. Maximum setting is 15 psig (should not set limit 
higher than 12 psig). Increase limit setting to decrease cycling.

Main air vent not working (one-pipe 
steam) or trap not working (two-pipe 
steam)

Contact service technician to check/replace main air vent or trap.

Frequent release of 
water through relief 
valve

Inoperative limit control

Call qualified service technician to replace limit control.

Need to frequently add 
makeup water

Leaks in boiler or piping

Have qualified service technician repair leaks at once to avoid constant use of makeup 
water. Makeup water can cause mineral deposits which, in turn, can cause boiler section 
failure.

Black water condition

Oxygen corrosion due to leaks in 
boiler and piping

Have qualified service technician repair at once. Keep pH of water between 7.0 to 8.5.

Popping or percolating 
noise heard in boiler

Mineral deposits in sections due to 
constant use of makeup water

Call qualified service technician to de-lime boiler, if necessary. In some cases, deposits will 
be too heavy to remove with de-liming procedures.

Have qualified service technician repair leaks to eliminate need for constant makeup water.

Incorrect pH of boiler water

Call qualified service technician to check pH level and correct. pH should be maintained 
between 7.0 to 8.5.

Water disappears from 
gauge glass and back 
out into system through 
return piping

Incorrect piping in Hartford loop

Call qualified service technician to inspect. Correct piping, if necessary, to agree exactly with 
Boiler Manual. Clean or replace check valve or vacuum breaker if required.

Check-valve inoperative or leaking

Vacuum breaker inoperative

Metal flakes found in 
vent outlet or vent — 
flueway corrosion

Contaminated combustion air supply 
— See page 2 in this manual.

Remove any contaminating products. See page 2 in this manual.

Provide outside air for combustion. Kit available through local distributor. Have qualified 
service technician pipe-up kit.

Condensation of combustion gases 
in boiler sections

Have qualified service technician inspect system piping and controls to verify proper 
regulation of return water temperature.

Some radiators or 
baseboard units do not 
heat

Main (or radiator) air vents (one-pipe 
steam) or traps (two-pipe steam) not 
operating correctly

Call qualified service technician to inspect/replace air vents or traps

High limit set too low

Adjust high limit to higher setting.

Violent waterline 
fluctuations or surging

Dirt, oil or other impurities in water

Call qualified service technician to skim boiler, referring to Boiler Manual for procedure.

Waterline too high

Correct waterline to maximum height of gauge glass, minimum height of ¼” above bottom 
of gauge glass.

Water passing into 
steam mains — priming

Incorrect piping

Call qualified service technician to inspect piping, correcting to exactly as shown in Boiler 
Manual, if not as shown.

Sudden release of boiler steam 
pressure by action of zone valves

Call qualified service technician to inspect, adjusting valves or replacing with slow-opening 
valves if necessary.

Domestic water from 
tankless heater is hot 
then suddenly turns 
cold.
— or —
Domestic water from 
tankless heater is 
always lukewarm.

Mineral deposits insulate internal 
waterways of heater

Have qualified service technician delime or replace coil.

Boiler stop-leak compound has been 
added to boiler water and is 
insulating outside of coil

Have qualified service technician remove and clean coil 

and

 drain and flush boiler to remove 

stop-leak.

Incorrect mixing valve setting for 
tankless heater

Have qualified service technician adjust mixing valve setting.

Domestic flow rate too high

Have qualified service technician install flow check valve set to rating of tankless heater.

Incorrect setting on tankless heater 
control

Have qualified service technician raise tankless control setting. Adjust differential on 
tankless control to lower setting.