18
Part Number 550-142-320/0720
GWA
Series 3
Gas-Fired Water Boilers –
Boiler Manual
4 Water piping — multiple zones
continued
Figure 14
Boiler-bypass piping
Zoning with circulators (Alternative to
primary/secondary piping
Figures
12 and 13)
Figure 15
Boiler-bypass piping
Zoning with zone valves (Alternative to primary/
secondary piping
Figures
12 and 13)
Water piping — low temperature systems
continued
1
Boiler
isolation (balancing) valves
2
Flow/check
valve
3
System
or zone circulator
4
System
temperature gauges
5
Zone
valve
6
Drain
valve
7
System
temperature valves (see instructions to the
left for adjusting valves)
8
Blend
temperature gauge
9
Relief
valve
10
Automatic
air vent (with diaphragm-type expansion tank), or
connect to tank fitting (closed-type expansion tank).
DO NOT
use an automatic air vent when using closed-type expansion
tank. It would allow air to leave the system, causing waterlog-
ging of the expansion tank.
11
Fill
valve
12
Diaphragm-type
or bladder-type expansion tank, if used (For
closed-type expansion tank, pipe from top of air separator to
tank fitting as in Figure 6, page 11
.
)
13
Air
separator and automatic vent, if used (Note that the fill valve
must always be connected to the expansion tank, regardless
of location of expansion tank, circulator or air separator.)