Williams 743511 Скачать руководство пользователя страница 11

 

Servicing 

All servicing activities must be carried out by a qualified service technicial or a service agency.  The home owner may not 

service the furnace. The home owner must read this section to be informed of the periodic maintenance and checks the 

required.    All servicing (except on vent system) must be carried out with the external casing removed.  After any servicing, the 

external casing must be reinstalled properly. 

Checking and Adjusting the Gas Manifold Pressure 

The furnace comes set from the factory at the correct HI and LO gas manifold pressures as shown in “Technical Data”.  It is 
recommended to check the pressures periodically (minimum once a year).  If adjustment is required, this can be done by 
adjusting screws C and D.  (Figure 8)   A test gauge must be connected as explained in “Checking the Gas Manifold Pressure”.   
 
Proceed as follows: 

1.  Place the unit on and in the HI mode (knob in HI position). 

2.  Adjust the HI pressure by turning the screw C (pressure regulator) to the value given in “Technical Data”.  Turn clockwise 

to increase the pressure, turn counterclockwise to decrease it. 

3.  Turn the control knob clockwise until the gas control switches to LO mode. The position in which this occurs depends on 

the actual room temperature. 

4.  Loosen screw D until the correct value for the LO pressure is achieved.  Turn clockwise to decrease the pressure, turn 

counterclockwise to increase it. 

5.  Switch the unit from LO to HI mode to check that both the HI and LO pressures are correct.  A tolerance of plus or minus 

0.1-inches w.c. on the pressure value is acceptable. Readjust if needed. 

6.  Disconnect the test gauge and tighten firmly the screw of the gauge connection, then check for gas leaks from it. 

The HI and LO pressures must be adjusted in the way explained above. Never try to adjust them independently from each other. 
 
 

Checking, Removing and Reassembling of the Vent Air Intake System 

It is essential that the vent air intake system is examined periodically (minimum once a year) to verify it is clean from dust and 
deposits of solid materials such as leaves or nests.  The vent air intake system is checked from outside.  Proceed as follows: 

1.  Remove the vent cap by removing the three outer screws.  (Figure 7) 

2.  Remove the inner flue pipe. 

 Do not use tools;

 the pipe can be extracted by hand. 

3.  Remove dust and desposits from the vent cap and flue pipes.  Deposits in the air pipe must be taken outside.  

Do not 

push them inside the furnace.  

The outer air pipe may not be removed from outside. 

4.  Reinstall the flue pipe from outside. Do not use glue or sealants. 

5.  Reinstall the vent cap on the flue pipe. Do not use glue or sealants. Tighten the three outer screws. 

 

Lubrication of Moving Parts

This furnace does not require lubrication.  Do not try to lubricate any part of the furnace such as motors bearings, keys, knobs, 
screws, etc. 
 

Flame Visual Check

Correct and proper operation of the burner may be checked by examinng the burner flame.  The flame may be examined 
through the front flame viewer.  The flame must be stable and have blue color.  Some small yellow tips are acceptable with 
propane gas.  If the flame is yellow or has excessive turbulence, check the gas manifold pressure and the vent air intake system. 
If all these are acceptable, call a qualified service technician for a complete check of the furnace.  Call also your gas supplier to 
check the composition of the gas in use. 

 

10 

Содержание 743511

Страница 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 0743512 MODEL Propane Gas Only 0743511...

Страница 2: ...to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code CSA B149 1 Mobile Manufacture...

Страница 3: ...ce technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas is a flammable g...

Страница 4: ...iff test of the LP Gas is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recomme...

Страница 5: ...as equipment in residential garages must be installed so that all burners and burner ignition devices are located not less than 18 inches 460 mm above the floor Such equipment shall be located or prot...

Страница 6: ...m 3 As specified in CGA B149 installation codes 1991 F Clearance to outside corner 12 inches 30 cm minimum Note Local codes or regulations may require different clearances G Clearance to inside corner...

Страница 7: ...is horizontal 6 Remove the casing from the furnace body unscrewing the two mounting screws Figure 3 7 Mount the largest tube diameter 4 inches 101 6 mm and the gasket on the unit frame with the screws...

Страница 8: ...Each furnace should have its own manual gas cock A manual main gas cock should be located in the vicinity of the unit Where none exists or where its size or location is not adequate contact your local...

Страница 9: ...h danger To prevent nuisance and operation of fire alarms ventilate the room for the first two hours of operation Checking the Gas Inlet Pressure The gas inlet pressure can be measured by connecting a...

Страница 10: ...rty damage personal injury or loss of life OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this labe 2 Turn gas control knob clockwise to OFF Do not force 3 Wait 5 minutes to clear...

Страница 11: ...nnect the test gauge and tighten firmly the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted in the way explained above Never try to adjust them...

Страница 12: ...06065 Sparking Candle Part Number JGLL064 Nozzle Natural Gas Part Number J12160880 Nozzle LPG Piezo Electric Button Part Number JPZO000 Thermocouple Part Number JTRM000D Burner Part Number J90021028 P...

Отзывы: