Williams 2001621A Скачать руководство пользователя страница 16

 

Operating Your Heater

 

 

16 

 

Start-Up Procedure 

Start the heater  using the procedures in the section “Operating 
Your Heater”. 

WARNING:

  Danger of bodily injury or death. L.P. 

Gas  is heavier than air and it will settle in any low 
area, including open depressions and it will remain 
there unless the area is ventilated.  
Never attempt to start-up the unit before thoroughly 
ventilating the area. 

 

Check the heater  operation as outlined in the following 
instructions. If any sparking, odors or unusual noises are 
encountered, shut off the electric power immediately. Recheck for 
wiring errors or obstructions in or near the fan motor. 

CHECK GAS INPUT AND PRESSURES 

For  heaters  located at elevations between sea level and 2,000 
feet, the measured input must not be greater than the input shown 
on the rating plate of the heater. For elevations above 2,000 feet, 
the measured input must not exceed the input on the rating plate 
reduced by 4

 

percent for each 1,000 feet that the heater is above 

sea level. 

Gas supply pressure and manifold pressure with the burners 
operating is specified on the rating plate. 

 

Rated input will be obtained on a heating value of 2,500 Btu/hr. for 
propane at 10-inches  manifold pressure with factory-sized 
orifices.  If L.P.  Gas having a different heating value is supplied, 
orifices must be changed by a qualified service technician before 
the heater is operated. 

CHECK THERMOSTAT 

Check  the  thermostat operation.  When set above room 
temperature shown on the thermostat, the main burner should 
light.  Make certain the thermostat turns off the heater  when the 
room temperature reaches the selected setting and starts the 
heater when the room temperature falls a few degrees. 

CHECK THE MANIFOLD GAS PRESSURE 

A tapped opening is provided in the gas valve to facilitate 
measuring the manifold gas pressure. A "U Tube" manometer 
having a scale range from 0 to 12-inches of water should be used 
for this measurement. The manifold pressure must be measured 
with the burner and pilot operating. Any major changes in flow 
must be made by changing the size of the burner orifice. 

Check with your local gas supplier for proper orifice sizing. 

CHECK THE GAS INPUT (NATURAL GAS ONLY) 

WARNING:

  Natural gas heating value (Btu  per 

cubic foot) can vary significantly.  Therefore, it is 
the installer's responsibility to see that Btu/hr. input 
to the heater is adjusted properly.  Failure to do so 
could cause combustion chamber failure, 
asphyxiation, fire or explosion resulting in damage, 
bodily injury or death.    Refer to the National  Fuel 
Gas  Code (NFPA  54) to be sure the heater  is 
burning fuel at the proper rate. 

 

Under firing could cause inadequate heat, excessive 
condensation or ignition problems. Over firing could cause 
sooting,  flame impingement or overheating of the combustion 
chamber. 

Before starting natural gas input check, obtain heating value of 
the gas (Btu per cubic foot) at standard conditions from your local 
supplier. 

 

To measure the input, using the gas meter, proceed as follows: 

1.  Turn off gas supply to all other appliances except the heater. 

2.  With the heater operating, time the smallest dial on the meter 

for one complete revolution.  If this is a 2-cubic-foot dial, divide 
the seconds by 2. If this is a 1-cubic-foot dial, use the time in 
seconds as is (3,600 = Sec/hr.).  This gives the seconds per 
cubic foot of gas being delivered to the heater.  

3.  Assuming natural gas with a heating value of 1,000 Btu  per 

cubic foot and 34-seconds per cubic foot used as determined 
by step (2), then: 

Input = 1,000 x 3,600 / 34 = 106,000 Btu/hr. 

 

This measured input must not be greater than the input 
indicated on the nameplate of the heater. 

4.  Relight all other appliances turned off in Step 1 above.   Be 

sure all pilots are operating. 

CHECK PILOT BURNER 

The pilot flame must envelop 1/2-  to 5/8-inches of the generator. 
Pilot flame is preset at the factory, so ordinarily does not require 
field  adjustment.  (Figure  17).  On new installations, the gas lines 
will be filled with air and may take several minutes to establish a 
pilot flame. 

 

 

 

 

 

 

 

 

Type of Gas 

Manifold Pressure, In. W.C. 

Natural 

4.0

 

L.P. 

10.0

 

 

FIGURE 17  Pilot Burner 

Содержание 2001621A

Страница 1: ...2A 3512922A 3532922A 3552922A 5001522A 5011522A 5031522A 5051522A 5001922A 5011922A 5031922A 5051922A 5002522A 5012522A 5032522A 5052522A 5002922A 5012922A 5032922A 5052922A 6501522A 6511522A 6531522A...

Страница 2: ...do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified installer and operated in accordance with the installation and homeown...

Страница 3: ...17 Operating Instructions 18 How To Care For Your Heater 19 20 Repair Parts Parts Lists 21 26 Blower Accessory 2102 27 28 Troubleshooting Chart 29 31 SERVICE HINTS Back Cover How To Order Repair Parts...

Страница 4: ...ing Follow the venting instructions for your type of installation exactly Use only the type and size of vent pipe and fittings specified 10 BE SURE to provide for adequate combustion and ventilation a...

Страница 5: ...er is design certified in accordance with American National Standard CSA Standard Z21 86 and CSA 2 32 as a vented room heater and must be installed according to these instructions Basic Tools Needed H...

Страница 6: ...to circulate around it Never install the heater in a wall recess The minimum clearance required to any wall or object can be found on the rating plate located inside the heater control door on the ba...

Страница 7: ...d on threaded pipe joints must be resistant to the action of liquefied petroleum gases WARNING When connecting field piping use a second wrench to keep the heater valve from turning Support field pipi...

Страница 8: ...blem and appliances could be starving for air In addition these energy measures mean that your home will retain more water vapor or a higher relative humidity High humidity especially during cold weat...

Страница 9: ...cial provisions are made such as ventilation grilles installed between connecting rooms Page 10 figure 8 shows the minimum area in square feet based on 8 foot ceiling heights required for different Bt...

Страница 10: ...square inch per 1000 Btu hr combined input of appliances in one room if combined input exceeds 100 000 Btu hr WARNING Danger of property damage bodily injury or loss of life The adjoining unconfined...

Страница 11: ...he location selected All wiring must agree with local codes and ordinances These instructions cover bringing the wire down from the attic but it can be run from a basement or crawl space using similar...

Страница 12: ...res are properly cleaned soldered and taped 7 Use 18 gauge wire as supplied for a maximum length of 20 feet If longer length is needed use 16 gauge wire for a maximum length of 25 feet 8 Connect the t...

Страница 13: ...ctly to the draft hood of the room heater when a clearance of 2 1 2 inches 64mm is maintained between the single wall vent pipe and the combustible wall of the room in which the room heater is located...

Страница 14: ...p out rain and snow and to prevent obstructions of the vent The vent cap will also prevent excessive downdraft that can cause carbon monoxide to enter into the home Do not use a homemade vent cap They...

Страница 15: ...Installing Your Heater FIGURE 15 Straight Up Venting With Type B Gas Vent FIGURE 16 Venting Into An Outside Type B Gas Vent 3 in 7 cm See Figure 1 C...

Страница 16: ...must be measured with the burner and pilot operating Any major changes in flow must be made by changing the size of the burner orifice Check with your local gas supplier for proper orifice sizing CHEC...

Страница 17: ...one blue color 1 2 to 3 4 inch above ports 2 Secondary inner cone light blue 1 to 2 inches above ports 3 Total flame from blue to nearly invisible approximately 6 inches above ports Abnormal Appearanc...

Страница 18: ...o the appliance 4 Remove the control access panel 5 Turn the gas control knob clockwise to OFF NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not use force 6 Wait fi...

Страница 19: ...ion and more effective heating do not place obstructions furniture or other items closer than four feet to the front of the cabinet or two feet from each side of the cabinet ANNUAL UPKEEP NEEDED It is...

Страница 20: ...earth assembly in place Grasp the assembly frame and pull forward 3 Remove the screws in the glass window frame IMPORTANT The logs are made of special lightweight materials that can be easily damaged...

Страница 21: ...Replacement Parts Accessories 21 FOR MODELS 2001621A 2011621A 2031621A 2051621A 2001622A 2011622A 2031622A 2051622A FOR PART LIST SEE PAGE 22...

Страница 22: ...0265 K000265 5 Valve Bracket K000850 K000850 6 Control Valve P322660 P323011 7 Burner K000851 K000851 8 Orifice Fitting P500086 P500086 9 Burner Orifice P501800 P501781 10 Pilot P323073 P323074 11 The...

Страница 23: ...Replacement Parts Accessories 23 ENCLOSED FRONT FOR PART LIST SEE PAGE 24...

Страница 24: ...t K000207 K000207 K000208 K000208 K000209 K000209 8 Wire Assembly P500409 P500409 P500416 P500416 P500416 P500416 9 Top Louver Assembly K000181 K000181 K000212 1 K000212 1 K000212 2 K000212 2 10 Combu...

Страница 25: ...Replacement Parts Accessories 25 FIREPLACE LOOK WITH LOGS FOR PART LIST SEE PAGE 26...

Страница 26: ...20 P501621 P501621 P501622 P501622 10 Control Bracket K000147 K000147 K000147 K000147 K000147 K000147 11 Burner Orifice P500081 P500351 P500360 P500345 P500330 P500432 12 Orifice Fitting P500086 P5000...

Страница 27: ...heater floor using the existing screw holes Align the opening in the base of the motor and blower with the opening in the heater floor The opening on the side of the motor and blower should align with...

Страница 28: ...operate When the heater cools down the blower will turn off The blower will not operate if the speed switch is set in the OFF center position Replacement Parts Reference Number Part Number Description...

Страница 29: ...lace the gas valve after above is verified 2 Pilot burning no gas to the main burner A Thermostat not turned to a position calling for heat Set the thermostat to a position calling for heat B Plugged...

Страница 30: ...at location Check thermostat location if on an outside wall or there is a hole in wall behind the thermostat causing cold air to contact the thermostat relocate the thermostat or plug the hole Check t...

Страница 31: ...place D Excessive flame roll out Heater is possibly overrated check for high gas pressure at gas valve see 4B E Burner is over fired Check the manifold gas pressure Check the rate this appliance is ma...

Страница 32: ...d exactly a fire or explosion may result causing property damage personal injury or loss of life Williams Furnace Company 250 West Laurel Street Colton CA 92324 909 825 0993 FAX 909 824 8009 www wfc f...

Отзывы: