5  Installation 

All pipes connecting to the tank should have removable connections (fitting/flange). Pipe thread seals with teflon are 
to be avoided. 
 

All tank connecting pipes are to be planned, constructed and tested according to the technical rules in force, as well as to the 
corresponding norms and regulations in accordance with their application and supply medium. 
 
It  is  recommended  to  foresee  a  decalcification  possibility  through  stop  valves  with  drain  possibility  or  t-piece  with  cold water 
inlet and hot water outlet of the DHW heat exchanger or a water softening device in highly calcareous water areas.

 

Appropriate  filters  should  be  used  to  prevent  dirt  or  particles  from  entering  the  tanks.  Moreover, the tank should be ensured 
against  pressure  fluctuations  and  excess  pressure  through  the  installation  of  tested  pressure  reducing  valves  and  safety 
valves. 
Sensors  and  thermostats  necessary  for  temperature  control  must  be  securely  and  permanently  positioned  on  the  tank 
(immersion sleeve and sensor rail). 
 
The tank’s venting and draining facilities must have the appropriate dimensions and be correctly installed. 
The installation company is responsible for the correct execution of work and for the safe and careful insulation of the pipes. 

 

When connecting to a solar plant, a temperature limiter is required and must be installed on site at the hot water outlet 
in order to prevent scalding.   

 

Connection scheme

 (according to DIN 1988) 

 

 

 

      

Illustration 2 (Schematic diagram) 

 

 
The size of the DHW safety valve is shown below: 
 

Content of DHW space 

Min. valve size 

Max. heating performance 

up to 200 l 

NW 15 (1/2“) 

75 kW 

above 200 to 1000 l 

NW 20 (3/4“) 

150 kW 

 

 

lllustration 3 (Schematic drawing– example hydraulic system heating) 

 

The thread diameter of the heating safety valve depends on the nominal capacity of the water space and the maximum heating 
capacity of the heat generator. It can be determined as follows: 
 

Reaction pressure 

Max. heating capacity of the heat generator 

1,5 bar 

36 kW 

72 kW 

144 kW 

252 kW 

433 kW 

650 kW 

2,0 bar 

43 kW 

86 kW 

172 kW 

302 kW 

518 kW 

778 kW 

2,5 bar 

50 kW 

100 kW 

200 kW 

350 kW 

600 kW 

900 kW 

3,0 bar 

56 kW 

112 kW 

224 kW 

395 kW 

678 kW 

1017 kW 

Thread diameter (inch) 

1/2 

¾ 

5/4 

6/4 

 

Содержание WIKOSOL 805

Страница 1: ...maintenance record must be entirely completed and the user has to be instructed accordingly Efficient operation can only be guaranteed if the instructions of this manual are followed Warranty does no...

Страница 2: ...alve outlet in width It may not have more than 2 bends and should not be longer than 2 m If for any compelling reasons 3 bends or a length up to 4 m are required then the entire exhaust line must be d...

Страница 3: ...80 1802 1520 1020 700 290 830 290 980 1020 700 290 1845 1520 Wikosol 805 2 790 990 160 1650 1880 1802 1520 1020 700 290 830 1490 290 1085 980 1020 700 290 1845 1520 Chart 1 W Tilting dimension Connect...

Страница 4: ...aterial DHW heat echanger W St 1 4404 Material tank S235JR Corrosion protection buffer Internal bare external coated with corrosion proof lacquer Performance tank fully loaded 65 C HV 70 C HW 45 C CW...

Страница 5: ...he tank immersion sleeve and sensor rail The tank s venting and draining facilities must have the appropriate dimensions and be correctly installed The installation company is responsible for the corr...

Страница 6: ...ozzles again Start up the heating system While the System is heating up water will leak out of the safety valve Before the handover of the system to the end user owner the plumbing contractor should e...

Страница 7: ...has been modified through the installation of externally supplied parts or through irregular professional maintenance Subject to our general terms and conditions Legal warranty 2 years Guarantee year...

Страница 8: ...operation and maintenance Place Date Customer Installer Signature Signature Place of installation Name ZIP Code Place Street Phone Tank model Serial number Date of invoice In the case of reclamation...

Отзывы: